Appendix M
:
Retrofitting onto a CL-5 Cooper
Siemens Industry, Inc.
80
Cooper Regulator Connection Notes:
1) The control cable signals comprise the
“Cooper Retrofit Cable” which connects
between the Cooper regulator (back panel) and the MJ- control panel.
2)
The MJ- contains all the necessary interface circuits for connecting directly to the
Cooper regulator back panel
–
no external circuit board is needed.
3)
“TB-2” refers to the Terminal Block 2 – located inside the Cooper control panel
enclosure.
4) For Cooper regulators, (Cooper) TB-
2 “VS” provides the “L” bushing voltage.
5)
For Cooper regulators, the “S” bushing voltage is derived from the (optional)
“differential PT.”
6) The connection from (Cooper) TB-
2 “V7” to (MJ-) P2A “P2” is only needed if
the regulator has a differential PT (for detecting the “S” bushing voltage).
MJ- Name
MJ- Terminal
Cooper Terminal
Description
HS
P2A-1
HS
Operation Counter
U112
P2A-2
NL
Neutral Pos. Switch
U2
P2A-8
VS
Sensing Voltage
C2
P2A-5
C3
Current Polarity
E
P2A-6
G
Voltage Ground
E1
P2A-7
C1
Current Ground
N/A*
*
VM*
Motor Voltage*
J
P2A-9
R3
Raise Output
K
P2A-10
L3
Lower Output
U11
P2A-12
DHR
Drag Hand Reset
* Typically, VM will be jumpered to VS inside the Cooper Control box.
Optionally, the jumper from P2B -11 to P2B-12 can be removed from the MJ- and VM can be
connected to P2B-11, U6 to provide a separate motor voltage to the MJ.
M: RETROFITTING AN MJ-XL or MJ-4A/MJ5 CONTROL PANEL ONTO A COOPER
VOLTAGE REGULATOR (CL-5 and earlier
)
Retrofit Kit Contents
- Instructions and drawing 21-116-601-233
- Cooper Hinges (2), part 21-116-601-229
- Cooper fanning strip wiring harness (1), part 21-116-601-233
- Metal Bracket (1), part 21-116-601-230
- Nylon spacer (1)
- Panel locking screw (1)
- Philips-head screws (6)
- Fuses: 6A(2), 0.75A(1)