4 Setting Up the MJ-5 Control Panel
Siemens Industry, Inc.
16
Table 4.2
The <
ADV CONFIGURE
> menu
DATA ITEM
DESCRIPTION
VALID INPUTS
DEFAULT
INC
Meter Volts
Display Primary or Secondary volts
SEC, PRI
SEC
---
I Threshold %
Tap change minimum current
0% to 10 %
0%
1%
I Shift
Current shift for reverse power flow
0˚ to 359˚
0˚
1 ˚
I Load Max
Max. Load Current (for Overcurrent)
0% to 350%
350%
1%
PT Threshold
Tap change low voltage limit
0 to 134
90
1%
Time
Time of day
HH:MM:SSA/P
---
---
Date
Date
NN/NN/NN
---
---
Format
Date format
Mo/Da/Yr or Da/Mo/Yr
Mo/Da/Yr
---
Daylight Savings
Daylight Savings Time
ON or OFF
ON
----
Dmd Type
Method for determining Demand
THERMAL or WINDOW
THERMAL
---
Dmd Time
Demand Period length (minutes)
1 to 999
30
1
Minute
Dmd Subperiods Number of Demand subperiods
1 to 99 (For Sliding Window mode only)
6
1
Min/Max t.o.
Min/Max display timeout (seconds)
1 to 99
15
1
Second
Screen t.o.
Show default display screen (min.)
1 to 99
5
1
Minute
Quick t.o.
Quick menu display timeout (second)
1 to 59
10
1
Second
QuickDispTim
Quick menu slideshow time (second)
1 to 10
2
1
Second
AutoVari-Amp
Automatic Vari-Amp Protection
ON or OFF
OFF
---
SoftVari-Amp
Sofware Vari-Amp setting
ON or OFF
OFF
---
R Limit
Raise Limit (Alert & Soft Vari-Amp)
10, 8
, 7
, 6
, 5 %
10%
1
%
L Limit
Lower Limit (Alert & Soft Vari-Amp)
10, 8
, 7
, 6
, 5 %
10%
1
%
Slave Master
Put two tap changer in locked step
(Ref. Comm. Manual Section 8)
OFF,MA,Sl,S2
OFF
Tap Alert
Enable or disable tap alerts
ENABLE or DISABLE
ENABLE
---
Alrt M=
Alrt C=
Alrt S=
Metering
Control
System
Y (to enable) or N (to disable)
Y (to enable) or N (to disable)
Y (to enable) or N (to disable)
Y
Y
Y
---
---
---
Tap Resync
Synchronizes tap position at Neutral
ON or OFF
OFF
---
Comm AutoInh
Turns SCADA auto inhibit ON or OFF
ON or OFF
OFF
---
Lower LED
Raise Lower Indicator Functionality
Solid, Blink
Solid
---
P2 Calc
P2 Calculation
ON, OFF
ON
---
U2/P2 Out
Load Voltage Terminal Locking
VLoad, Toggle, U2, P2
VLoad
---
I Dir Bias
Current Bias Functionality
None, Fwd, Rev, Neut T
None
---
Bias %
Current Bias Percent
0 to 10%
0%
---
Remote BTN
Remote/Local Button Functionality
Enabled, Disabled
Enabled
---
Macntrl
Master slave control voltage
(Ref. Comm. Manual Section 8)
Master, Highest, Lowest, Average