Appendices
Appendix F - Measuring Consumption (kWh), Demand, and Other Applications
67
Siemens Industry, Inc.
125-201
09/30/2019
00120
C \NAME FOR THE HISTORICAL FORECAST IS ................ ........(VLAO,HST)\HST\
00122
C \NAME FOR THE CALCULATION INTERVAL IS ............... ........(VLAO,CLC)\CLC\
00124
C \NAME FOR THE SLIDING WINDOW INTERVAL IS ....................(VLAO,WND)\WND\
00126
C \NAME FOR THE PLOT SECTION (TIME VS. DEMAND) ............(VLAO,PLT)\PLT\
00128
C \NAME FOR THE END TIME OF PEAK DEMAND LIMIT 1 IS .......(VLAO,TM1)\TM1\
00130
C \NAME FOR THE END TIME OF PEAK DEMAND LIMIT 2 IS ........(VLAO,TM2)\TM2\
00132
C \NAME FOR TOTAL KW AVAILABLE FOR PDL STATEMENT ......(VLAO\KW1)\KW1\
00134
C \NAME FOR PDL STATEMENT TARGET .................. ............(VLAO\TG1)\TG1\
00136
C
00138
C VIRTUAL DIGITAL OUTPUTS
00140
C
00142
C \NAME FOR THE OUTPUT POINT FOR EXCEEDING THE DEMAND LIMIT ...(VLDO,EX)\EX\
00984
C
00986
C-------SET UP THE NAME OF THE MECHANICAL SYSTEM-------
00988
C APOGEE INSTRUCTIONS: REPLACE %X% WITH MECHANICAL SYSTEM.
00990
C NON-APOGEE PANEL: DELETE OR "COMMENT OUT" LINE 1000 AND
00992
C USE "SEARCH AND REPLACE" TO CHANGE %X% TO MECHANICAL SYSTEM
00994
C NAME (MAXIMUM OF 3 CHARACTERS) IN THE PROGRAM.
00996
C NOTE: BRIEF: TOGGLE REGULAR EXPRESSIONS OFF (CNTRL F6) TO FIND %.
00998
C
01000
DEFINE(X,”%X%”)
01010
DEFINE(U,”DEM:DEMAND”)
01094
C
01096
C SUBMETER ACTUAL READING
01098
C
01100
%X%KW = $PDL
01194
C
01196
C MONITOR OF THE SUBMETER
01198
C
01200
PDLMTR (”%X%ARE”, ”%X%HST”, ”%X%CLC”, ”%X%WND”, ”%X%PLT”,0,”%U%”,
-1)
01294
C