![Siemens LOGO! Manual Download Page 56](http://html.mh-extra.com/html/siemens/logo/logo_manual_377208056.webp)
LOGO! installation and wiring
2.3 Wiring LOGO!
LOGO!
56
Manual, 04/2011, A5E03556174-01
2.3.4
Connecting outputs
LOGO! ...R...
The LOGO! ...R... version is equipped with relay outputs. The potential of the relay contacts
is isolated from the power supply and the inputs.
Requirements for relay outputs
You can connect various loads to the outputs; e.g., lamps, fluorescent lamps, motors,
contactor relays, etc. For information on the properties required for the loads connected to
LOGO! ...R..., refer to the technical data (Page 319).
Connecting
This is how you connect the load to LOGO! ...R... :
//
'05
4
4
4
4
10
3URWHFWLRQZLWKDXWRPDWLFFLUFXLWEUHDNHUPD[$FKDUDFWHULVWLFV%
HJ3RZHUFLUFXLWEUHDNHU6;LIUHTXLUHG
/RDG
/RDG
LOGO! with solid-state outputs
LOGO! versions with solid-state outputs can be identified by the fact that the letter R is
missing from their type name. The outputs are short circuit-proof and overload-proof. An
auxiliary load voltage supply is not necessary, because LOGO! supplies the load voltage.
Requirements for solid-state outputs
The load connected to LOGO! must have the following characteristics:
●
The maximum switched current is 0.3 A per output.
Summary of Contents for LOGO!
Page 8: ...Preface LOGO 8 Manual 04 2011 A5E03556174 01 ...
Page 278: ...LOGO functions 4 4 Special functions list SF LOGO 278 Manual 04 2011 A5E03556174 01 ...
Page 366: ...Abbreviations LOGO 366 Manual 04 2011 A5E03556174 01 ...
Page 372: ...Index LOGO 372 Manual 04 2011 A5E03556174 01 ...
Page 534: ...Index Basic Panels 162 Operating Instructions 04 2012 A5E02421799 03 ...