Configuring the HMI device
5.1 Configuring devices with graphical Control Panel
Basic Panels
Operating Instructions, 04/2012, A5E02421799-03
69
5.1.3
Changing MPI/DP settings
Note
The settings for MPI or PROFIBUS DP communication are defined in the HMI device project.
Edit the transfer settings only in the following situations:
•
Initial transfer of a project.
•
Changes made to the project are activated at a later time.
A
A
1.
Press "MPI / Profibus Settings" to
open the "MPI / Profibus Settings"
dialog.
2.
Deactivate the "Panel is the only
master on the bus" check box if
additional masters are connected
to the bus.
3.
Enter the bus address for the HMI
device in the "Address" text box.
The bus address must be unique
within the MPI/PROFIBUS DP
network.
Enter the time limit for PROFIBUS
communication in the "Time-out"
text box.
Valid values are 1 s, 10 s and
100 s.
4.
Select the transmission rate from
the "Transmission Rate" text box.
Enter the highest station address
on the bus in the "Highest Station"
text box. Valid range of values: 1 to
126.
Select the profile from the "Profile"
selection box.
Press the "Bus Parameters..."
button to view the PROFIBUS
profile data.
5.
Close the dialog and save your
entries with "OK".
Summary of Contents for LOGO!
Page 8: ...Preface LOGO 8 Manual 04 2011 A5E03556174 01 ...
Page 278: ...LOGO functions 4 4 Special functions list SF LOGO 278 Manual 04 2011 A5E03556174 01 ...
Page 366: ...Abbreviations LOGO 366 Manual 04 2011 A5E03556174 01 ...
Page 372: ...Index LOGO 372 Manual 04 2011 A5E03556174 01 ...
Page 534: ...Index Basic Panels 162 Operating Instructions 04 2012 A5E02421799 03 ...