![Siemens LOGO! Manual Download Page 331](http://html.mh-extra.com/html/siemens/logo/logo_manual_377208331.webp)
Technical data
A.6 Technical data: LOGO! 24RC...
LOGO!
Manual, 04/2011, A5E03556174-01
331
LOGO! 24RC
LOGO! 24RCo
Range
- -
max. Input voltage
- -
Digital outputs
Number
4
Output type
Relay outputs
Electrical isolation
Yes
In groups of
1
Control of a digital input
Yes
Continuous current I
th
max. 10 A per relay
Surge current
max. 30 A
Incandescent lamp load (25000 switching
cycles) at
1000 W
Fluorescent tubes with ballast (25000
switching cycles)
10 x 58 W
Fluorescent tubes, conventionally
compensated (25000 switching cycles)
1 x 58 W
Fluorescent tubes, uncompensated (25000
switching cycles)
10 x 58 W
Derating
none; across the entire temperature range
Short circuit-proof cos 1
Power protection B16, 600A
Short circuit-proof cos 0.5 to 0.7
Power protection B16, 900A
Parallel output circuits for power increase
Not permitted
Protection of output relay
(if desired)
max. 16 A,
characteristic B16
Switching rate
Mechanical
10 Hz
Ohmic load/lamp load
2 Hz
Inductive load
0.5 Hz
Notice: For fluorescent lamps with capacitors, the technical data of fluorescent lamp ballasts
must also be considered. If the maximum allowed surge current is exceeded, fluorescent
lamps must be switched with appropriate contactor relays.
The data was determined with the following devices:
Siemens fluorescent tubes 58W VVG 5LZ 583 3-1 uncompensated.
Siemens fluorescent tubes 58W VVG 5LZ 583 3-1 parallel compensated with 7μF.
Siemens fluorescent tubes 58W VVG 5LZ 501 1-1N with ballast.
Summary of Contents for LOGO!
Page 8: ...Preface LOGO 8 Manual 04 2011 A5E03556174 01 ...
Page 278: ...LOGO functions 4 4 Special functions list SF LOGO 278 Manual 04 2011 A5E03556174 01 ...
Page 366: ...Abbreviations LOGO 366 Manual 04 2011 A5E03556174 01 ...
Page 372: ...Index LOGO 372 Manual 04 2011 A5E03556174 01 ...
Page 534: ...Index Basic Panels 162 Operating Instructions 04 2012 A5E02421799 03 ...