LOGO! functions
4.3 Special Functions
LOGO!
152
Manual, 04/2011, A5E03556174-01
Accuracy of T
Because of slight tolerances in the characteristics of electronic components, the set time T
can deviate. You can find a detailed description of such deviations in the "On-delay" topic
(Page 160).
Accuracy of the timer (weekly/yearly timer)
To prevent timing inaccuracy of the real-time clock in C versions caused by this deviation,
the timer value is continuously compared with a high-precision timebase and corrected. The
resultant maximum timing inaccuracy is ±2 s/day.
4.3.3
Backup of the real-time clock
Because the internal real–time clock of a LOGO! is backed up, it continues operation after a
power failure. The ambient temperature influences the backup time. At an ambient
temperature of 25°C, the typical backup time of a LOGO! 0BA6 is 80 hours and the typical
backup time of a LOGO! 0BA7 is 20 days.
If there is a power outage of a LOGO! for more than 80 hours (if 0BA6) or 20 days (if 0BA7),
the internal clock responds, dependent on the equipment series, as shown below:
●
Equipment series 0BA0:
On restarting, the clock is set to "Sunday 00:00 1 January". The time starts to run. Due to
this, the system processes the time switches, which trigger actions if necessary.
●
Equipment series 0BA1 to 0BA6:
On restarting, the clock is set to "Sunday 00:00 1 January". The time is stopped and
flashes. LOGO! is back in the status that it was in before the power outage. In RUN
mode, the system processes the counters that were parameterized with the time above.
The clock is, however, still stopped.
●
Equipment series 0BA6:
If you are using the optional LOGO! Battery card, or combined LOGO! Memory/Battery
card, LOGO! can retain the clock time for up to two years. These cards are available for
equipment series 0BA6.
●
Equipment series 0BA7
On restarting, the clock is set to "Sa 00 00 2011-01-01". The time is stopped and flashes.
LOGO! is back in the status that it was in before the power outage. In RUN mode, the
system processes the counters that were parameterized with the time above. The clock
is, however, still stopped.
Summary of Contents for LOGO!
Page 8: ...Preface LOGO 8 Manual 04 2011 A5E03556174 01 ...
Page 278: ...LOGO functions 4 4 Special functions list SF LOGO 278 Manual 04 2011 A5E03556174 01 ...
Page 366: ...Abbreviations LOGO 366 Manual 04 2011 A5E03556174 01 ...
Page 372: ...Index LOGO 372 Manual 04 2011 A5E03556174 01 ...
Page 534: ...Index Basic Panels 162 Operating Instructions 04 2012 A5E02421799 03 ...