![Siemens LOGO! Manual Download Page 24](http://html.mh-extra.com/html/siemens/logo/logo_manual_377208024.webp)
Getting started with LOGO!
LOGO!
24
Manual, 04/2011, A5E03556174-01
Versions
The following LOGO! versions are available:
Symbol
Designation
Supply voltage
Inputs
Outputs
Properties
LOGO! 12/24RCE
12/24V DC
8 digital
1)
4 relays
(10 A)
(0BA7)
LOGO! 230RCE
115 ... 240 V
AC/DC
8 digital
4 relays
(10A)
LOGO! 12/24RC
12/24 V DC
8 digital
1)
4 relays
(10 A)
LOGO! 24
24 V DC
8 digital
1)
4 solid state
24V / 0.3A
no clock
LOGO! 24C
24 V DC
8 digital
1)
4 solid state
24V / 0.3A
LOGO! 24RC
3)
24 V AC/
24 V DC
8 digital
4 relays
(10A)
LOGO! 230RC
2)
115 ... 240 V
AC/DC
8 digital
4 relays
(10A)
LOGO! 12/24RCo
12/24 V DC
8 digital
1)
4 relays
(10A)
no display unit
no keyboard
LOGO! 24o
24 V DC
8 digital
1)
4 solid state
24 V / 0.3A
no display unit
no keyboard
no clock
LOGO! 24Co
24 V DC
8 digital
1)
4 solid state
24 V / 0.3A
no display unit
no keyboard
LOGO! 24RCo
3)
24 V AC / 24 V DC 8 digital
4 relays
(10A)
no display unit
no keyboard
LOGO! 230RCo
2)
115 ... 240 V
AC/DC
8 digital
4 relays
(10A)
no display unit
no keyboard
1)
Of those can be used alternatively: 4 analog inputs (0 ... 10V) and 4 fast digital inputs.
2)
230 V AC versions: Two groups consisting of 4 inputs each. Each input within a group must be
connected to the same phase. It is possible to interconnect groups with a different phase.
3)
The digital inputs can be operated with P or N action.
Summary of Contents for LOGO!
Page 8: ...Preface LOGO 8 Manual 04 2011 A5E03556174 01 ...
Page 278: ...LOGO functions 4 4 Special functions list SF LOGO 278 Manual 04 2011 A5E03556174 01 ...
Page 366: ...Abbreviations LOGO 366 Manual 04 2011 A5E03556174 01 ...
Page 372: ...Index LOGO 372 Manual 04 2011 A5E03556174 01 ...
Page 534: ...Index Basic Panels 162 Operating Instructions 04 2012 A5E02421799 03 ...