Expansion modules
The following expansion modules can be connected to LOGO!:
Symbol Name
Power supply
Inputs
Outputs
LOGO! DM8 12/24R 12/24 V DC
4 digital
4 relays (5A)
LOGO! DM8 24
24 V DC
4 digital
4 solid state 24V /
0.3A
LOGO! DM8 24R
3)
24 V AC/DC
4 digital
4 relays (5A)
LOGO! DM8 230R
115 ... 240 V AC/DC
4 digital
1)
4 relays (5A)
LOGO! DM16 24
24 V DC
8 digital
8 solid state
24V / 0.3A
LOGO! DM16 24R
24 V DC
8 digital
8 relays (5A)
LOGO! DM16 230R 115 ... 240 V AC/DC
8 digital
4)
8 relays (5A)
LOGO! AM2
12/24 V DC
2 analog
0 ... 10V or
0/4 ... 20mA
2)
None
LOGO! AM2 PT100 12/24 V DC
2 PT100
6)
-50 degrees C to
+200 degrees C
None
LOGO! AM2 RTD
12/24 V DC
2 PT100 or 2 PT1000
or 1 PT100 plus 1
PT1000
6)
-50 degrees C to
+200 degrees C
None
LOGO! AM2 AQ
24 V DC
None
2 analog
0 ... 10 V DC or
0/4...20mA
5)
1)
Different phases are not allowed within the inputs.
2)
0 ... 10 V, 0/4 ... 20 mA can be connected optionally.
3)
Digital inputs can be operated either with P or with N action.
4)
Two groups consisting of 4 inputs each. Each input within a group must be connected to the same
phase. It is possible to interconnect groups with a different phase.
5)
0 ... 10 V, 0/4 ... 20 mA can be connected optionally. The 0/4 ... 20 mA current output is only
possible with the LOGO! 0BA6 Base Module.
6)
Sensors supported by the LOGO! AM2 RTD module are the PT100 and PT1000 sensors with a
default temperature coefficient α of 0.003850.
Summary of Contents for LOGO!
Page 8: ...Preface LOGO 8 Manual 04 2011 A5E03556174 01 ...
Page 278: ...LOGO functions 4 4 Special functions list SF LOGO 278 Manual 04 2011 A5E03556174 01 ...
Page 366: ...Abbreviations LOGO 366 Manual 04 2011 A5E03556174 01 ...
Page 372: ...Index LOGO 372 Manual 04 2011 A5E03556174 01 ...
Page 534: ...Index Basic Panels 162 Operating Instructions 04 2012 A5E02421799 03 ...