Troubleshooting/FAQs
4.2 Alarm Letter Codes and Descriptions
SITRANS FUH1010 Quick Start
Operating Instructions (Compact), 12/2008, CQO:QSG010 Revision A
37
4.2
Alarm Letter Codes and Descriptions
Letter Code
Alarm
Description
S
Spacing
Transducer spacing may need readjustment.
0
ZeroMatic
ZeroMatic signal fault.
E
Empty
Pipe is empty.
R
Rate
Flow above High setting or below Low setting.
F
Fault
Three continuous seconds without new data update.
A
Aeration
Current aeration percentage exceeds the alarm set point.
M
Memory
Last valid reading for a selected interval during Fault condition.
K
Makeup
In-Process Makeup occurred.
I
Interface
Liquid Vs exceeds interface alarm set point.
P
Pig
Pig passage detected (optional).
The display shown below indicates where the Alarm Codes appear on the LCD display
screen.
PV
6
①
Alarm Codes