Specifications
8
Technical data
82
Building Technologies
007016_i_en_--
Fire Safety
2012-09-07
8
Specifications
8.1
Technical data
FDnet/C-NET-detector line
Operating voltage
DC 12…33 V
Operating current (quiescent)
0.8 mA
Maximum current connection factor
4
Quiescent current connection factor
4
Address connection factor
1
Separator connector factor
1
Protocol
FDnet/C-NET
Compatibility
See 'List of compatibility'
Collective detector line
Operating voltage
DC 14…28 V
Operating current (quiescent)
0.7 mA
Making current
Max. 1.5 mA
Connection factor
10
Alarm voltage at alarm current:
1 … 15 mA
DC 5…10 V
35 mA
DC 18…22 V
50 mA
DC 26…28 V
Alarm current at operating voltage DC 5 … 28 V 4 … 50 mA
Reset voltage
DC 2…4 V
Reset time at reset voltage DC 2 V
1…2 s
Protocol
Collective (with and without current
limitation)
Compatibility
See 'List of compatibility'
Line separator
Line voltage:
Nominal
DC 32 V (= V
nom
)
Minimum
DC 12 V (= V
min
)
Maximum
DC 33 V (= V
max
)
Voltage at which the separator opens:
Minimum
DC 7.5 V (= V
SO min
)
Maximum
DC 10.5 V (= V
SO max
)
Permanent current when switches are closed:
Max. 0.5 A (= I
C max
)
Switching current (e.g., in the event of a short-
circuit)
Max. 1 A (= I
S max
)
Leakage current when switches are open:
Max. 1 mA (= I
L max
)
Serial impedance when switches are closed:
Max. 0.5 Ω (= Z
C max
)