
Planning
4
Planning in rooms with inclined ceilings
38
Building Technologies
007016_i_en_--
Fire Safety
2012-09-07
Distance between detector and ceiling (3): Define the distance between the
detector and the ceiling depending on the room height. See [➙ 43]
Installation surface: Define the installation surface given the architectural
circumstances. The installation surface must be stable and vibration-free. See
If the room has one or more of the following circumstances, you must also observe
further information.
Ceiling with uneven inclines: The detector must be slid sideways to the flatter
roof incline. See [➙ 39]
Narrow spatial circumstances: Maintain the minimum distance (2) between two
detectors. See [➙ 47]
Girders: The detector can be installed in the ceiling panel between the girders
or below the girders. See [➙ 47]
Glass panes: Detection through glass panes and installation on glass panes
are only possible under restricted circumstances. See [➙ 49]
Danger of moisture condensation: Use the detector heating unit if there is a
danger of moisture condensation. See [➙ 50]
Extraneous light: Use the extraneous light filter in the case of extremely strong
extraneous light. See [➙ 51]
Infrared ray in the gable
In the case of ceilings with an inclination of n > 0.5, you must always install an
infrared ray in the gable. In the case of ceilings with an inclination of n < 0.5, the
infrared ray is not necessary in the gable.
Left: Ceiling with inclination of n > 0.5. Right: Ceiling with inclination of n < 0.5