Commissioning
6
Checking the signal level and distance
70
Building Technologies
007016_i_en_--
Fire Safety
2012-09-07
6.6
Checking the signal level and distance
The detector line is switched on.
1. Loosen the two safety screws (3).
2. Make sure that the vertical scale (7) and the horizontal scale (1) are centered
(factory setting). Otherwise the scales must be re-adjusted with the knurled
screws:
- the vertical scale (7) with the knurled screw (8)
- the horizontal scale (1) with the knurled screw (2).
3. Set the 'Adjust' menu with the button (4) on the adjustment device.
4. Read the indicators for the signal level and the distance from the adjustment
device:
- If the signal level is over 100 and the distance indication matches the
detection distance, continue fine-tuning the detector optics.
- If the signal level is below 100 and/or the distance indicator does not match
the detection distance, continue with preliminary setting of the detector
optics.