Commissioning
6
Initializing the detector
76
Building Technologies
007016_i_en_--
Fire Safety
2012-09-07
4. Activate the initialization procedure by pressing the button (3). The detection
distance must not be interrupted during initialization!
During initialization, the following is displayed on the adjustment device:
Initialization
....................
Following successful initialization, 100 % ±3 % and the effective detection
distance is displayed on the adjustment device. Example:
100%
50m
OK
5. Copy the standardized signal value onto the two labels.
50 1133 100
FDL241-9; commissioning & adjustment data
(values displayed on adjustment device)
distance
[m]
deviate-
signal
[%]
covered-
reflector
value
[%]
values
date &
action
signal-
value
[-]
100%
50m
OK
The detector is initialized.
Troubleshooting during initialization
If the standardized signal value is not within 100 % ±3 % or if the detection
indication displayed deviates by more than 10 % from the effective detection
distance, repeat the initialization process from step 4.
If initialization fails, the following is displayed:
Initialization
failed
Remedy the error and repeat the initialization process. Possible causes for
failed initialization:
Signal
Possible cause
Not stable
Moving obstacle
Too high
Strong reflection
Too low
Detection distance too large
Reflector too small
Reflector aligned incorrectly
Reflector covered