Reflector for middle distance (foil) DLR1192 and reflector for short
distance (foil) DLR1193
The reflectors for middle distance and for short distance consist of a foil with micro-
prismatic elements, which are formed in a transparent, synthetic resin, sealed and
mounted on a plastic base. The foil has the same principal effect as the prism.
See also
Detection distance and reflector selection [➙ 40]
3.3.3
Line separator
All FDnet/C-NET devices are equipped with a line separator.
The FDnet/C-NET device is equipped with electronic switches which isolate the
defective part in case of a short-circuit on the detector line. The rest of the detector
line remains serviceable. On a loop line all FDnet/C-NET devices remain fully
functional after a simple error.
3.3.4
Danger levels
The detector can transmit the following danger levels to the control panel:
Danger level
Meaning
Comment
0
No danger
Normal condition
1
1
Check situation
You may have to select another
parameter set.
You may have to re-initialize the
detector.
2
1
Warning
Possible danger
3
Alarm
Fire
The evaluation of the danger level and the decisions to be taken (e.g. activation of
remote transmission) are configured in the control panel.
1
Danger levels 1 and 2 are only transmitted to FDnet/C-NET detector lines. On a
collective detector line, only danger levels 0 and 3 can be transmitted to the control
panel.