Commissioning
Installing the reflectors for middle distance and short distance (foil)
6
63
Building Technologies
007016_i_en_--
Fire Safety
2012-09-07
6
Commissioning
Sequence
1. Set parameter set
2. Install detector unit
3. Install detector heating unit (optional)
4. Insert filter in detector (optional)
5. Commissioning the adjustment device
6. Checking the signal level and distance
7. Preliminary setting of the detector optics (optional)
8. Fine-tuning of the detector optics
9. Initializing the detector
10. Testing detectors
The types are described in the following chapters.