Mounting / Installation
Installing the reflector for long distance (prism)
5
61
Building Technologies
007016_i_en_--
Fire Safety
2012-09-07
5.4
Installing the reflector for long distance (prism)
WARNING
Danger of falling
Bodily injury
● When installing, use a secured ladder or work platform.
-
+
-
+
1
2
3
Installing the reflector
1 Base
3 Terminals for heating unit
2 Prism unit
Installation without heating unit
The installation location of the reflector is defined according to the planning
information.
1. Install the base (1) with two screws on a level surface.
2. Install the prism unit (2) on the base with four screws.
The reflector is installed.
Installation with heating unit
Note the positive and negative poles.
Only connect one wire per terminal. This is the only way of ensuring a problem-
free connection over the device's entire service life.
The installation location of the reflector is defined according to the planning
information.
You need a 24 V supply for the heating. Only use cables with a wire diameter
of 0.2…1.5 mm
2
.
1. Break open the plastic parts in the base (1) at the openings you require for
cable entry.