Specifications
Technical data
8
59 | 66
Building Technologies
007011_m_en_--
Fire Safety
2018-06-28
Line separator
Line voltage:
Nominal
DC 32 V (= V
nom
)
Minimum
DC 12 V (= V
min
)
Maximum
DC 33 V (= V
max
)
Voltage at which the line separator
opens:
Minimum
DC 7.5 V (= V
SO min
)
Maximum
DC 10.5 V (= V
SO max
)
Permanent current when switches are
closed
Max. 0.5 A (= I
C max
)
Switching current
(e.g., in the event of a short-circuit)
Max. 1 A (= I
S max
)
Leakage current when switches are
open
Max. 1 mA (= I
L max
)
Serial impedance when switches are
closed
Max. 0.5 (= Z
C max
)
External alarm indicators
Number of external alarm indicators
that can be connected
2
Voltage
DC 6…17 V
Current
9…15 mA
Length of line
Max. 30 m with unshielded
cables (recommended) or if
the shielding on the detector
is connected to the positive
pole for the external alarm
indicator
Max. 5 m, if the shielding is
connected to earth
Flashing interval times on
FDnet/C-NET detector line:
Bright
15 ms
Dark
1 s
Flashing interval times on collective
detector line
Control panel-specific
Device characteristics
Number of sensors:
3
Connections
Detector line:
Design
Socket strip
Conductor cross section
0.2…1.5 mm
2
External alarm indicators:
Design
Socket strip
Conductor cross section
0.2…1.5 mm
2