Commissioning
Commissioning an addressed detector line
6
51 | 66
Building Technologies
007011_m_en_--
Fire Safety
2018-06-28
6.1.2 Set parameter set
Once the detector line has been read in, you need to set the parameter set. When
in FDnet/C-NET operation, the DIP switches in the flame detector are not active.
Use the control panel to set the parameter set you want. The table below shows
the parameter sets and associated numbers.
No.
Parameter set
01 Robust
02 Universal
03 Universal
fast
04 Sensitive
05 Sensitive
fast
06 Rapid
07 Motor test bed
14 Download
1
15 Download
2
Table 3: Parameter sets for FDF241-9
The procedure for setting the parameter set via the control panel is described in
the control panel documentation.
See also
2
6.1.3 Run performance check
Use test lamp LE3 or a test fire to check the function of the flame detector.
The procedure control is described in the chapter 'Performance check [ 55]'.
See also
2