Maintenance / Repair
Cleaning
7
56 | 66
Building Technologies
007011_m_en_--
Fire Safety
2018-06-28
Performance check with a test fire
WARNING
Fire hazard from test fire
Bodily injury and material damage
Only specially trained persons may undertake test fires. These persons must
be trained in how to handle fire extinguishers.
The size of the test fire depends on the room height.
1. On the control panel, switch off the remote transmission of alarms. To do this
set the 'Detector test' operating mode on the control panel.
2. Use a test fire to test the flame detector. Note the information in
document 009977.
a
The flame detector activates an alarm within 20 seconds.
a
The alarm indicator on the flame detector flashes.
3. On the control panel, switch the remote transmission of alarms back on.
a
The flame detector is ready.
You will find more detailed information in the fire detection system documentation.
If the flame detector does not activate an alarm, follow the actions described in the
'Repair [ 57]' chapter.
See also
2
7.2 Cleaning
The flame detector sensors must be clearly visible through the protective glass.
Proceed as follows if this is not the case:
1. Clean the protective glass from the outside with a soft, damp cloth. Washing-up
liquid may be used if the glass is very dirty.
2. Carry out a function check [ 55].
See also
2