Specifications
Technical data
8
58 | 66
Building Technologies
007011_m_en_--
Fire Safety
2018-06-28
8 Specifications
8.1 Technical data
You will find information on approvals, CE marking, and the relevant EU directives
for this device (these devices) in the following document(s); see 'Applicable
documents' chapter:
Document 007012
FDnet/C-NET detector line Operating voltage
DC 12…33 V
Operating current (quiescent)
0.7 mA
Maximum current connection factor 3
Quiescent current connection factor 3
Address connection factor
1
Separator connector factor
1
Protocol
FDnet/C-NET
Compatibility
See 'List of compatibility'
Collective detector line
Operating voltage
DC 14…28 V
Operating current (quiescent)
0.5 mA
Making current
Max. 0.75 mA
Connection factor
5
Alarm voltage at alarm current:
1…15 mA
DC 5…10 V
35 mA
DC 18…22 V
50 mA
DC 26…28 V
Alarm current at operating voltage
DC 5…28 V
4…50 mA
Reset voltage
DC 2…4 V
Reset time at reset voltage DC 2 V
1…2 s
Protocol
Collective (with and without
current limitation)
Compatibility
See 'List of compatibility'