Structure and function
Function
3
23 | 66
Building Technologies
007011_m_en_--
Fire Safety
2018-06-28
3.3.3 Messages to the control panel
The flame detector can transmit the following messages to the control panel:
FDnet/C-NET operation
Message
Meaning
Measures
Danger level '0'
Normal condition
-
Danger level '3'
The flame detector has
detected a fire and
transmits an alarm to the
control panel.
-
'Error'
The flame detector is
defective. Fire detection is
no longer ensured.
Replace the flame
detector.
'Incorrect parameter'
A parameter set which is
not available has been
set.
Fire detection is no longer
ensured.
Select the correct
parameter set.
Collective operation
Message
Meaning
Measures
'Alarm' danger level
The flame detector has
detected a fire and
transmits an alarm to the
control panel.
-
'Fault'
The parameters for
the flame detector are
set incorrectly.
OR
The flame detector is
defective.
Fire detection is no longer
ensured.
Set the parameter set
correctly.
OR
Replace the flame
detector.
The text shown in the messages may differ due to country-specific adaptations
and control panel versions.
See also
2