Planning
Determine parameter set
4
37 | 66
Building Technologies
007011_m_en_--
Fire Safety
2018-06-28
4.4.1 Parameter sets for FDF241-9
The table below shows the parameter sets for flame detector FDF241-9:
Parameter set
Sensitivity
Integration
Resistance to deceptive phenomena
No. Name
Solar radiation
Hot
objects
Arc welding
01 Robust
Normal (class 2)
Very long
X
X
X
02 Universal
Normal (class 2)
Medium
X
X
X
03 Universal
fast
Normal (class 2)
Short
X
X
X
04 Sensitive
High (class 1)
Medium
–
X
–
05 Sensitive
fast
High (class 1)
Short
–
–
–
06 Rapid
High (class 1)
Very short
–
–
–
07 Motor test bed
High (class 1)
Very long
–
X
–
14 Download
1
Application-specific parameter set
15 Download
2
Application-specific parameter set
Table 2: Parameter sets for flame detector FDF241-9
Typical applications for parameter sets
Robust (01)
This parameter set is suited to halls where deceptive phenomena such as flying
sparks, molten metals or strong solar radiation can be expected. Examples:
Foundry, hardening shop, electric arc welding site, open ferry boat.
Universal (02)
This parameter set is suited to rooms where a normal fire growth can be expected.
Examples: Battery room, machine room on ships, transformer station.
Universal fast (03)
This parameter set is suited to rooms where a rapid fire growth can be expected
and there is a high danger to life. Example: Warehouse for chemicals.
Sensitive (04)
This parameter set is suited to large halls or outdoor applications where a normal
fire growth can be expected. Examples: Industrial storage room, print shop, wood
storage, atrium, recycling facility, ferry, cargo ship, tunnel.
Sensitive fast (05)
This parameter set is suited to halls and sites where a rapid fire growth can be
expected and where even the smallest of flames will result in major damage.
Examples: Fuel storage room, pumping station, petrochemical facility, aircraft
hangar.
Rapid (06)
This parameter set is suited to protection of physical assets. Small flames possibly
caused by processes must be detected immediately. The risk of false alarms is
accepted. Example: Conveyor belt transporting combustible products from a
furnace to the packaging area.