NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the
Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be
limited to specific values or not used at all as indicated below.
Program Feature or Option
Possible Settings
Settings Permitted in UL 864
Supervision/Trouble Resound
Not enabled
0-30 hours
Yes
1-24 hours
DACT Phone Line Settings
Disable 1 phone line connection
Enable both phone line connections
Manual Release delay
10-60 seconds
10-30 seconds
DACT supervision time
1 hour, 6 hours and 24 hours
6 hours or less
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in
CAN/ULCS527, Standard for Control Units for Fire Alarm Systems, certain programming features or options must be limited to
specific values or not used at all as indicated below.
Program Feature or Option
Possible Settings
Settings Permitted in CAN/
ULC-S527
Supervision/Trouble Resound
Not enabled
0-30 hours
Yes
1-24 hours
DACT Phone Line Settings
Disable 1 phone line connection
Enable both phone line connections
Manual Release delay
10-60 seconds
10-30 seconds
Panel Buzzer On
Check/Uncheck (default)
Uncheck
firealarmresources.com
Summary of Contents for FC2005
Page 5: ...firealarmresources com ...
Page 33: ...28 FC2005 Enclosure Mounting Pictures firealarmresources com ...
Page 48: ...43 firealarmresources com ...
Page 58: ...53 This page is left intentionally blank firealarmresources com ...
Page 89: ...84 LE4010 CF Configuration Reference from DSC Installation Manual firealarmresources com ...
Page 90: ...85 TL300 CF Configuration Reference from DSC Installation Manual firealarmresources com ...