83 

WIRING DIAGRAM FOR DSC’S TL300CF AND LE4010CF 
CONNECTION, INCLUDING TROUBLE REPORTING ROUTE

 

 

 

firealarmresources.com

Summary of Contents for FC2005

Page 1: ...A6V10333722_m_en_ 2021 12 28 Smart Infrastructure Fire Alarm Control Panel Model FC2005 Installation Operation and Maintenance Manual firealarmresources com ...

Page 2: ...8 Universal Enclosure for Annunciators FTH2073 UA 8 SLC ADDRESSABLE DEVICES 9 Smoke Detector 9 Heat Detectors 9 Addressable Modules Monitor and Control 9 Manual Stations 9 Sounder Base 9 Programming SLC Devices 10 PAD 5 10 EVENT HISTORY 11 GENERAL DESIGN FEATURES 12 Environmental 12 Power Limiting 12 Ground Fault Detection 12 NAC Operation 12 Security Features 12 REGULATORY STANDARDS 13 Underwrite...

Page 3: ...Main Board Package 24 3 FC2005 Configuration Kit Package 25 4 FC2005 product documentation 25 CONTROL PANEL LOCATION 26 INSTALLATION 26 Enclosure Mounting 26 Remove Knock Outs 29 Power Supply FP2011 U1 Mounting 30 Ground Wire Installation 31 Battery Installation 32 Optional City Tie Mounting 33 Main Board Assembly Installation 34 Earth Cable Installation 34 SYSTEM WIRING 35 AC Connection 35 Batter...

Page 4: ...NDIX E APPLICATION SPECIFIC DETECTION 66 APPENDIX F TESTING MAINTENANCE 67 APPENDIX G LCD CONTROLS AND INDICATORS 68 Panel in US 68 Panel in Canada 68 Communication Port Connector 69 LEDS Buzzer and Dedicated Push Buttons 69 LCD Display 72 APPENDIX H OUTPUT FEATURES 74 Output Activation and Deactivation Delays 74 APPENDIX I PAS PRE SIGNAL 75 PAS 75 Pre Signal 76 APPENDIX J DACT INFORMATION OVERVIE...

Page 5: ...firealarmresources com ...

Page 6: ... and alarm power or after 4 years whichever happens first These batteries must be checked for performance at least two 2 times a year or more often if local requirements dictate Even though this control panel was made to last for the expected life of the fire alarm system any part could fail at any time Therefore a regular test program should be followed and documented to make sure that each part ...

Page 7: ...ease delay 10 60 seconds 10 30 seconds DACT supervision time 1 hour 6 hours and 24 hours 6 hours or less NOTICE TO USERS INSTALLERS AUTHORITIES HAVING JURISDICTION AND OTHER INVOLVED PARTIES This product incorporates field programmable software In order for the product to comply with the requirements in CAN ULCS527 Standard for Control Units for Fire Alarm Systems certain programming features or o...

Page 8: ...isn t practical the telephone company will notify the customer as soon as possible Also you will be advised of your right to file a complaint with the FCC if you believe it is necessary 3 The telephone company may make changes in this facilities equipment operations or procedures that could affect the operation of the equipment If this happens the telephone company will provide advance notice in o...

Page 9: ... spécifications techniques d Industrie Canada ont étérespectées Il ne garantit pas que le matériel fonctionnera àla satisfaction de l utilisateur NOTICE The Ringer Equivalence Number REN for this terminal equipment is 0 1 The REN assigned to each terminal equipment provides an indication of the maximum number of terminals allowed to be connected to a telephone interface The termination on an inter...

Page 10: ...sh to French or Spanish it is recommended but not necessary to create a new French or Spanish configuration and upload it to the panel The FC2005 features one LCD screen which is used to indicate the specific indications for system events while LEDs indicate general panel status FC2005 supports surface mounting and semi flush mounting Semi flush mounting kits are available for the enclosure System...

Page 11: ...ocol Serial Interface Circuit UFP The FC2005 control panel has a Serial Interface Circuit that can connect up to 8 devices e g remote LCD annunciators LED driver tabular annunciator or remote printer module Status Relays Four relays with dry contacts are provided Three relays are dedicated to alarm supervisory and trouble conditions on the panel The remaining relay is programmable The relay contac...

Page 12: ...etary systems Note For printer connection wiring between the RPM and printer must be in conduit within 6 feet and in the same room as the panel AUXILIARY MODULES Serial LCD Annunciators The FSD901 Serial LCD Annunciator consists of a backlit 160 by 64 dot 7 by 26 characters LCD display acknowledge silence unsilence and reset buttons a four way button for event navigation seven system status LED in...

Page 13: ... in Canada a separate ULC listed power supply PAD 4 or PAD 5 must be installed adjacent to the FC2005 or FC901 panel to power the FT2018 U1 R1 or FT2019 U1 R1 annunciator See Appendix N for PAD 4 Wiring Instruction When configuring the FT2018 U1 R1 or FT2019 U1 R1 for Canadian applications it must be programmed as a local device so that lamp test can be initiated from panel When annunciator FT2018...

Page 14: ...sing may be the most effective detection method The heat detectors may be programmed for rate of rise operation or fixed temperature Addressable Modules Monitor and Control In addition to detectors the circuit can communicate with addressable monitor and control modules Monitor modules allow remote contact closure initiating devices to generate event conditions on the system Control modules provid...

Page 15: ...urce the power supply unit must be UL Listed for fire use only Power Limited and rated 19 28 VDC Audible signals are synchronized on zone basis Use sounder base in addition to panel NAC or PAD5 NAC when multiple alarm tones are needed in one zone Programming SLC Devices SLC devices can be assigned their electronic address and be tested by using the DPU Device Programmer Loop Tester PAD 5 The Model...

Page 16: ...splay by operating menu controls from the panel The history event log can also be transferred from the panel to a computer using the FXS901 U2 system configuration tool Events recorded in the history are Alarm trouble supervisory and status conditions Signal silence un silence Manual System reset User level login logout Start and stop of quick test Expiration of quick test Timer Trouble supervisor...

Page 17: ...er Ground Fault Threshold 5 kΩ System City Tie Ground Fault Threshold 5 kΩ System City Tie Ground Fault Threshold 5 kΩ SLC grounding detection threshold SLC Ground 5 kΩ SLC Ground 5 kΩ NAC Operation The notification appliance circuits are controlled by the system microprocessor in accordance with the site specific system configuration The notification appliance circuits can operate audible and vis...

Page 18: ...nd government regulatory agencies as noted Underwriters Laboratories The FC2005 control panel is listed under UL 864 Tenth Edition and to be installed in Accordance with the applicable National Fire Protection Association Installation Standard for NFPA 72 and NFPA 2001 Underwriters Laboratories of Canada The FC2005 control panel is listed under ULC S527 11 Third Edition Amendment 1 and to be insta...

Page 19: ...ax Filtered and Regulated Secondary Power Supply 24 V lead acid battery set Max charged voltage 27 8 VDC Automatic low battery disconnect voltage 19 2 0 1 VDC Max charge current 0 45 A Battery capacity 12 Ah for US and Canada internally to 18 Ah for US only with separate enclosure FH2072 UA Supervised Auxiliary Power Outputs Non resettable power output Power limited Current 0 75 A Voltage 19 to 28...

Page 20: ...1 0 A 8 0 Ω 0 5 A 16 0 Ω Alarm voltage 16 to 32 VDC Maximum ripple 0 1 VAC Used for special application only Two Class B or one Class A Total Max Current 2 5 A Serial Interface Circuit UFP Power limited Supervised Maximum wire loop resistance 50 Ω total Physical layer RS485 SLC Addressable Device Circuits Max 32 VDC Power limited Supervised Max current 0 07 A RMS Maximum wire loop resistance 50 Ω ...

Page 21: ...lus wire resistance 22 5 Ω Leased line Output 1 Normal output voltage 19 28 VDC open circuit condition Trouble output voltage 0 V Alarm output voltage 19 28 VDC open circuit condition Maximum wire resistance 2 5 kΩ Maximum short circuit current 25 mA Leased line Output 2 Normal output voltage 19 28 VDC open circuit condition Supervisory output voltage 19 28 VDC open circuit condition Maximum wire ...

Page 22: ...E IP GSM US NAPCO Starlink SLE LTEVI CFB IP GSM US NAPCO Starlink SLE LTEVI CFBPS IP GSM US NAPCO Starlink SLE LTEAI CFBPS IP GSM US NAPCO Starlink SLE LTEAI CFB IP GSM US NAPCO Starlink SLE LTEAI FIRE IP GSM US B465 Bosch IP GSM US DSC TL300CF IP 29007636 29007842 Canada DSC LE4010CF GSM Canada CAUTION To reduce the risk of fire use only No 26 AWG or larger telecommunication line cord Only to a l...

Page 23: ...d by the codes and control panel programming The notification appliances will be de activated and the Silenced LED in US Signal Silence LED in Canada will be off Press the button again to unsilence the previously silenced notification appliances POSITIVE Alarm Sequence PAS not supported under ULC standard Activation of an initiating device in an input group programmed for PAS activates the Alarm L...

Page 24: ...nts and the local panel buzzer activates in specific pattern that distinguishes the event from an alarm event Refer to the applicable section of the system manual to determine the probable cause of the trouble and the action to be taken Operating the Acknowledge Buzzer Silence button will silence the local panel buzzer and change the LED trouble indicator from flashing to steady The LCD display wi...

Page 25: ...nd users of the supervisory condition If the FC2005 is configured as Supervisory self restoring the system shall return to the System Normal status when the supervisory condition is restored unless there are additional events on the system If the FC2005 is not configured as Supervisory self restoring the system reverts to standby condition only after the RESET button is pressed firealarmresources ...

Page 26: ... LCD test From 4 to 7 seconds LEDs test From 7 to 10 seconds buzzers test Operator doesn t need to turn it off manually Lamp test will automatically quit when it completes For Canadian Installations the lamp test is also applicable to the FT2018 or the FT2019 LED Annunciator dedicated to the FC360 History The last 1000 system events are time tagged and recorded for review in the user level event h...

Page 27: ...lashes and LCD displays trouble conditions Panel buzzer sounds in trouble pattern To acknowledge the trouble Press the Acknowledge Buzzer Silence button The Trouble LED turns on steady and the buzzer turns off When the trouble condition has been cleared you need to reset the panel to restore to a normal standby condition if panel is not configured as Trouble self restoring When panel is configured...

Page 28: ...prevents the alarm from being silenced for a predetermined time To reset panel after alarm When the alarm condition is corrected return the panel to normal standby operation by pressing the Reset button Trouble Operation Trouble is indicated by Trouble LED flashes and LCD displays trouble conditions Panel buzzer sounds pulsing To acknowledge the trouble Enable the control buttons by operating the ...

Page 29: ... enclosure Description Qty FC2005 enclosure red 1 Installation instruction 1 T45 key 2 8 32 grounding cable nut 2 2 FC2005 Main Board Package Description Qty FC2005 main board 1 FC2005 main board support frame 1 FC2005 English film 1 FC2005 English strip 1 FC2005 rubber key 1 FC2005 battery bracket left optional 1 FC2005 battery bracket right optional 1 FC2005 battery cable 1 FC2005 battery cable ...

Page 30: ...T2018 U1 FT2018 R1 FT2019 U1 FT2019 R1 Installation instructions A6V11269908 FT2008 U1 FT2008 R1 FT2009 UI FT2009 RI Installation instructions A6V10456397 FTH2073 UA Installation instructions A6V11272327 FTH073 VP Installation instructions A6V11320548 FHC901 U1 Installation instructions A6V11569585 FH2072 UA Installation instructions A6V11272329 FXS901 Tool user manual A6V10336897 FT2007 S1 Instal...

Page 31: ...LLATION The enclosures must be fastened securely to a clean dry shock free and vibration free surface in a protected environment Consider the following when mounting the box Mounting height for visual and manual access to the Display Board Weight and size of backbox Local mounting codes When mounting the backbox position the backbox clear of obstructions so that the door can open freely and so tha...

Page 32: ...olts Mark drill and install the two bottom bolts in the backbox Tighten all four bolts securely against the back wall of the backbox If a semi flush mount installation is desired use the Semi flush Trim for the FC2005 The backbox can be mounted up to 3 1 2 inches into the wall Place the semi flush trim around the backbox and affix to the wall with four 10 x 3 4 inch wood screws provided with trim ...

Page 33: ...28 FC2005 Enclosure Mounting Pictures firealarmresources com ...

Page 34: ...Power limited and non power limited wiring must be run in separate conduit Attach conduit if required and run wires as required Label each field cable for future reference Basic system wiring and detector location must be in accordance with NFPA 72 or other instructions from the appropriate local authority having jurisdiction Unit connections and limitations are as indicated on the wiring diagrams...

Page 35: ... Supply FP2011 U1 Mounting Secure the power supply to the back of enclosure using the four provided 8 32 x 3 8 screws AC Input terminals must be located at the right side of the enclosure firealarmresources com ...

Page 36: ...e Installation Install one end of the grounding cable on the enclosure back box Install the other end of the grounding cable on the enclosure outer door Enclosure back box Enclosure outer door firealarmresources com ...

Page 37: ...y bracket if required to the back of enclosure using the eight provided 8 32 x 3 8 screws Recommended battery size Length 5 94 inch Width 3 86 inch Height 3 7 inch A separate enclosure must be used if a battery set larger than 12 AH in the FC2005 is required The FH2072 UA CAB BATT or any enclosure UL Listed for Fire Protective Signaling Use may be used firealarmresources com ...

Page 38: ...he city tie cable between city module and main board 2 4 screws Spacer T2 T1 T3 City tie module Detail A T1 T2 T3 Detail A City tie cabling X2 Output 2 Connect to T2 X3 Output 1 Connect to T3 From left to right TP1295 TP1294 TP1293 TP1292 Detail T1 From 1 to 4 TP1295 TP1294 TP1293 TP1292 1 2 3 4 firealarmresources com ...

Page 39: ...re using the four provided 8 32 x 3 8 screws Earth Cable Installation Connect the earth cable to the backbox and connector at the upper left corner of the main board 4 8 screws Secure the nut on the stud Plug the earth cable on the connector on the main board firealarmresources com ...

Page 40: ...arth bonding point or another good ground acceptable to the authority having jurisdiction and the electrical inspector The neutral wire must be taken back to the electrical panel neutral distribution bar Battery Connection WARNING Improper battery connections or shorting battery terminals may damage the system and or batteries and may cause personal injuries The control panel uses a 24V battery se...

Page 41: ...thin the FC2005 enclosure then the following guidelines do not apply In that case be sure to follow standard wiring practices Wiring Entering Enclosure Non Power Limited Wiring Wiring entering the enclosure from the right side of the backbox is considered non power limited wiring Wiring must be in the shortest route and must not overlap any other wiring Power Limited Wiring Wiring entering the enc...

Page 42: ...h high voltage and non power limited wiring running in separate conduit openings from power limited wiring Internal Structure AC input NAC 2 NAC 1 P2 Dialer Relay 1 Relay 2 7 Optional field wire knock outs Power limited Non power limited Relay 3 Relay 4 Enclosure Power supply Batteries Battery bracket left Battery bracket right Main board assembly firealarmresources com ...

Page 43: ...ply FP2011 A1 Power input for PCBA USB port Battery connector Brownout GND 26 GND L N G Connect to Main board with provided power cable Earth GND Neutral Grounding conductor AC Connect to power supply with power cable provided by factory for main board power input Battery Connections Supervised Non Power Limited For FC2005 24 V Battery Set 12 to 18 AH Non Power Limited For local programming operat...

Page 44: ...table terminal interrupts the power for 5 seconds after a reset condition Auxiliary Power Outputs Max 0 75 A 24 VDC nominal Supervised Power Limited X1_P X1_N X2_P Auxiliary power outputs X2_N Resettable Non resettable EARTH S_BN S_BP EARTH S_AN S_AP X2_P X2_N X1_P X1_N EARTH SE_B SE_A GND1 EARTH PR_B PR_A GND1 CT_P CT_N LL_SP LL_SN N_BP N_BN N_AP N_AN DACT PORT1 DACT PORT2 S_NO S_CO S_NC U_NO U_C...

Page 45: ...the open circuit a PAD 5 device power must be used When using an annunciator with the 50pt panel use the non resettable power supplied from the Fire Alarm Control Panel FACP When the annunciator is located too far from the FACP use a Battery backed up UL approved Power Supply to ensure continuous and proper operation firealarmresources com ...

Page 46: ...ed for special application only Two Class B or one Class A Total maximum current 2 5 A Refer to Desigo_NACs_A6V10333530_c_en to determine synchronized notification appliances allowed per NAC Class B Supervised Power Limited See Appendix B for compatible devices EOL available in the package as part of accessory 24K 0 5W resistor N_AN N_AP N_BN NAC N_BP Same as above Class A Supervised Power Limited...

Page 47: ...evice Power The on board auxiliary power can provide power for ONLY one annunciator If more power is required for the connected devices external power must be provided Each address on the circuit must be fully powered from either auxiliary power of control panel or external power If the annunciator is connected to a separate Power Supply the separate power supply needs to be UL Listed for Fire Saf...

Page 48: ...43 firealarmresources com ...

Page 49: ...o preserve the integrity of the data The following diagrams show the proper wiring Class B DCLB SE_A B PR_A B Control Panel In Out Annunciator In Out Annunciator In Out Annunciator In Out Annunciator In Out Annunciator In Out Annunciator Class A DCLA SE_A B PR_A B Control Panel In Out Annunciator In Out Annunciator In Out Annunciator firealarmresources com ...

Page 50: ...s all device addresses for alarm and trouble conditions Addressable Device Circuit Class B DCLB or Class A DCLA or Class X DCLC Operation Max 50 devices can be connected to the circuit Wire Resistance Max 50 Ohm See Appendix A Line Resistance Graph Supervised Power Limited See Appendix B for Compatible Devices S_AN S_AP S_BN P2 addressable device S_BP Addressable device EARTH EARTH firealarmresour...

Page 51: ...LASS B or ULC DCLB S_AN S_AP S_BN S_BP ISOLATOR MODULE SEE NOTE SEE NOTE SEE NOTE ISOLATOR MODULE SEE NOTE SEE NOTE SEE NOTE ISOLATOR MODULE SEE NOTE SEE NOTE SEE NOTE TO OPTIONAL BRANCH ES OF LOOP CIRCUIT SUPERVISED POWER LIMITED SUPERVISED POWER LIMITED PORT B SUPPORTS THE SAME WIRING AS PORT A PORT A PORT B Notes Siemens SLC Devices Detectors Monitor Modules or Control Modules up to a maximum o...

Page 52: ... devices recommended between Isolator Modules A Maximum of 15 Isolator Modules per addressable device circuit If more than one HCP is used on a SLC device loop the loop must be wired Class A DCLA or the riser conductors must be installed in accordance with the Survivability From Attack By Fire requirements in the National Fire Alarm Code NFPA 72 If wired Class A DCLA at least one HLIM loop isolato...

Page 53: ...ISED POWER LIMITED PORT A PORT B Notes Siemens SLC Devices Monitor Modules or Control Modules up to a maximum of 50 devices Only listed Class X DCLC devices models XTRI R XTRI D XTRI S XTRI M ILED XW ILED XC TSM 1X and PAD 5 can support CLASS X DCLC mode And all these devices must be wiring as isolator module If Class X DCLC devices are mixed with existing devices or wiring as non isolator module ...

Page 54: ...mited CT_P CT_N LL_SP City tie LL_SN Master Box CT_P CT_N LL_SP Leased line LL_SN leased line alarm trouble detection circuit leased line supervisory detection circuit DACT Wiring FC2005 will provide two connections to Public Switched Telephone Network PSTN Panel RJ31X RJ31X Telephone line 1 Telephone line 2 Optional output to tel Optional output to tel firealarmresources com ...

Page 55: ...software is available to allow programming the control panel by connection to a Personal Computer PC with an USB port This allows ease of operation by preparing the program in advance and downloading to the control panel in a simple rapid operation PROGRAMMING SECURITY The following levels of security protect the system from unauthorized use Level 1 User Locked Door Level 2 Maintenance Locked Door...

Page 56: ...ides control functions Level 3 Protected by level 3 password Level 3 provides control functions and parameter change functions The following functions are accessible to L2 and L3 user by selecting items in the Operate menu Disable Enable Devices Disable Enable NACs Disable Enable City Tie Disable Enable DACT Disable Enable Status Relays Disable Enable Detector Applications Disable Enable PAS Start...

Page 57: ...tc 7 After setting all Quicktest parameters and while still in the Quicktest screen Press the Menu button 8 Press the OK button to initialize Quicktest Note The countdown timer will be indicated in the upper right corner of the main board display Test conditions will be annunciated on the panel to indicate that panel is in Quick Test Mode Initiation of any addressable device will not activate asso...

Page 58: ...53 This page is left intentionally blank firealarmresources com ...

Page 59: ...8 08 16 5 08 14 3 19 12 2 01 NEC Chapter 9 Table 8 Addressable Device Circuit Wire Selection Guide Each addressable device circuit must meet the following requirements Total loop resistance 50 Ohm maximum with 50 devices Total loop capacitance 0 5 uF max line to line per km and 1 0 uF max line to shield per km Note The terminal blocks of Siemens SLC devices are rated for a maximum of 14AWG wire fi...

Page 60: ...ZE CALCULATIONS System Current Draw Break down System Current Draw Components Standby A Alarm A Main board 0 1590 0 1864 NAC 0 C1 SLC C2 C3 Auxiliary power C4 C5 City tie module 0 0017 0 0158 firealarmresources com ...

Page 61: ...TRI D 0 00050 0 00095 XTRI M 0 00050 0 00050 XTRI S 0 00050 0 00065 ILED XC 0 00050 0 00050 ILED XW 0 00050 0 00050 TSM 1X 0 00050 0 00050 PAD 5 MB 0 00075 0 00075 PAD 5 CLSA 0 00125 0 00125 PAD 5 CDC 0 00075 0 00075 Pull station 0 00050 0 00050 Total Standby Current 0 1590 C2 C4 0 0017 if used Total Alarm Current 0 1864 C1 C3 C5 0 0158 if used Where C1 NAC1 current NAC2 current should be less or ...

Page 62: ...g UL 69 2 5 Exception 2 30 Minutes of Alarm Operation per ULC AH for Alarm A X Hours A H for Standby A H for Alarm Calculated A H De rating Factor 20 derating per UL864 A H Required Battery Capacity X 1 2 Notes 1 An additional multiplier is included to compensate for the higher discharge rate in alarm Battery capacity decreases with age 2 Total standby current is limited to 0 247 A for Canada and ...

Page 63: ...x XMS SA x x x x Line modules HTRI S Single input interface module x x x x HTRI D Dual input interface module x x x x HTRI R Single input interface module with relay x x x x HTRI M Mini single input interface module x x x x HCP Intelligent control point x x x x HZM Conventional zone module x x x x HLIM Line isolator x x x x Alarm devices DB2 HR x x x x ADBH 11 Detector Audible base x x x x SBGA 34...

Page 64: ... x FDOT421 Smoke heat detector x x FDT421 Heat detector x x FD182UL Cerberus version Point detectors OP921 Smoke detector x x OH921 Smoke heat detector x x HI921 Heat detector x x ASA Global Sinteso version FDOOT441 Dual optical thermal multi sensor detector x x 4 FDOOTC441 Dual optical thermal CO multi sensor detector x x FDCIO422 Input output module x x x x ASA Global Cerberus version OOH941 Dua...

Page 65: ...d the first and last HCP See the HLIM installation instructions for the maximum number of isolators allowed per loop and other wiring instructions 4 FC2005 support FDOOTC441 CO functionality CO channel can be configured as automatic alarm event and supervisory event in the detection tree of the FC2005 But it does not comply with UL 2017 standard when the CO channel is configured for an automatic a...

Page 66: ...r display Desigo black FSD901 R2 Floor repeater display Desigo red FSD901 U3 Floor repeater display Cerberus black FSD901 R3 Floor repeater display Cerberus red FCA2018 U1 Remote Peripheral Module FT2018 U1 LED annunciator 16 Zone black FT2018 R1 LED annunciator 16 Zone red FT2019 U1 LED annunciator 32 Zone black FT2019 R1 LED annunciator 32 Zone red CO signaling can only be annunciated by panel N...

Page 67: ...ice Response More than one SLC device has the same address TypeUnknown The device type is unknown to the panel Dirty The SLC device is dirty Replace The SLC device needs to be replaced ParameterError The SLC device has invalid parameter setting AddressInvalid The address of SLC device is invalid AddressUnspecified The SLC device has no address ACFail The AC power of the system is in trouble Messag...

Page 68: ...DACT Bypass The configured DACT module stops working Addressable Device Bypass The input and output channel for configure P2 point stops working NAC Bypass The configured NAC stops working Fire Drill The system is performing a fire drill Manual Evac Manual fire alarm CO Test Corresponding detector s CO channel is set to be the most sensitive Lamp Test Start a lamp test ClearHistory Delete all hist...

Page 69: ...d Power to the detector is reapplied and time is allowed for detector to become operational for alarm CD Confirmation Period Detector is operational for alarm at point C If detector is still in alarm at point C FACP will report alarm If detector is not in alarm system returns to standby If the detector re alarms at any time during the confirmation period the FACP will alarm immediately The duratio...

Page 70: ...ge Alarm Verification Execution OP921 17 Configurable 1 60 s Configurable 60 125 s Panel OH921 17 OOH941 27 OOHC941 27 HFP 11 Depends on the device Configurable 1 60 s Depends on the device Device HFPO 11 SFP 11 Only available in Canada SFPO 11 Only available in Canada HZM Depends on the device SZM Only available in Canada PAD 5 CDC module firealarmresources com ...

Page 71: ...S of H series ASD Application ASD Description Disable No Applications Standard Photo thermal Detector Office Retail Reasonably clean climate controlled atmosphere Warehouse Light Manufacturing Airborne dust equipment fork truck and light to medium dock area exhaust fumes Lobby Relatively clean area temperature changes cellular phones smoking Computer Room Very controlled environment clean temperat...

Page 72: ...icable local codes BATTERY MAINTENANCE Perform the following tests at the recommended interval Replace the battery set every four years or if any of the test criteria are not met Initiation Reacceptance 1 Charger Test with the batteries fully charged and connected to the charger measure the voltage across the battery set It must read 27 3 V 0 3 V 2 Discharge Test with full system alarm load the vo...

Page 73: ...INDICATORS The FC2005 has a buzzer 7 LEDs 4 navigational push buttons 4 push buttons alphanumeric keypad 3 menu control buttons menu cancel and ok and a communication port connector Panel in US Panel in Canada firealarmresources com ...

Page 74: ...are in normal status OFF The system is not powered on This LED can be OFF only when the system is shut down Flashing The main power is in trouble and system is powered via battery 3 Silenced US Signal Silence Canada Yellow Steady ON All outputs which can be silenced are silenced OFF There are no silenced outputs in system Flashing Both silenced and unsilenced outputs exist 4 Trouble Yellow Steady ...

Page 75: ...o execute user defined and configured functions Alarm Signal Activation Canada Press button 8 to report the alarm zone events to the panel 9 Silence Unsilence US Press The button toggles between silence and unsilence Press button 9 to silence the audible and or visual notification appliances where permitted by the codes and control panel programming The notification appliances will be de activated...

Page 76: ...71 FXS901 U2 programming tool 16 Menu Press Menu button for PMI operation 18 Four way button Press A four way button for menu navigation firealarmresources com ...

Page 77: ... L1 Access level 11 15 System time 2 V Possible display V The event is acknowledged The event is unacknowledged ALM Current event type ManualAlarm Specific current event type Manu Connects to the content in line 3 3 al Alarm Zone1 Event location see complete information together with the last 4 characters in line 2 I Possible display I O in or out flag 4 V Possible display V The event is acknowled...

Page 78: ...larm event amount 004 SUP Supervisory event amount 006 TBL Trouble event amount 000 OTH Other event amount RCtl1 60 RCtl2 60 Releasing timer and releasing count down time 60 s by default Max 60 s DIS discharge is displayed after count down Event displaying rules Events are displayed according to the following rules 1 Events priority Unacknowledged Alarm Unacknowledged Supervisory Unacknowledged Tr...

Page 79: ...e during activation delay will not respond to deactivate command This means an output device with activation delay will definitely be activated after receiving activate command Output device during deactivation delay will respond to activate command immediately and the deactivation delay will be cancelled Assuming an output channel on SLC is configured to be interlocked by supervisory condition of...

Page 80: ...ng for a manual acknowledgement response If no response is received within 15 seconds the panel proceeds to activate the associated remote outputs See Figure A If the alarm event is acknowledged during the PAS delay time the programmable PAS investigation time 60 180 seconds is added to the PAS delay time before remote outputs are activated See Figure B However if a 2nd alarm is initiated anytime ...

Page 81: ...larm is initiated anytime during the Pre Signal delay time see figure below 1st Alarm Initiated 2nd Alarm Initiated Panel Reset Pre Signal Delay time Figure A Figure B When 2nd Alarm is Initiated Audible ON Audible OFF Audible ON Audible OFF Pre Signal Normal Sequence Pressing the reset button at anytime during the Pre Signal sequence will initiate a reset condition and restore the panel to stand ...

Page 82: ...st account does not respond after the programmed number of attempts busy account not responding etc the DACT will automatically attempt to send the event to the second account providing the event is set to report for that account The DACT may be configured for connection to lines that are set up for Rotary and or Tone dialing See the FC2005 Programming Manual P N 315 0494033 for details Must Can M...

Page 83: ...end event to Account 1 but is unsuccessful N Account 1 Account 2 Step 3 Panel keeps trying to send event to Account 1 until the programmed Number Of Attempts has been reached Step 4 Panel switches to Account 2 and attempts to transmit but is unsuccessful too N Account 1 Account 2 Step 5 Panel keeps trying to send event to Account 2 until the programmed Number Of Attempts has been reached Done If b...

Page 84: ...Account 1 but is unsuccessful N Account 1 Account 2 Step 3 Panel keeps trying to send event to Account 1 until the programmed Number Of Attempts has been reached Step 4 Panel switches to Account 2 and attempts to transmit but is unsuccessful too N Account 1 Account 2 Step 5 Panel keeps trying to send event to Account 2 until the programmed Number Of Attempts has been reached Done firealarmresource...

Page 85: ...eeds on Account 1 the first time Step 1 Panel goes into alarm Step 2 Panel tries to send event to Account 1 successful Y Account 1 Account 2 Step 3 Panel does NOT attempt to send event to Account 2 since Account 2 is set for Can Report and the event was transmitted to Account 1 successfully firealarmresources com ...

Page 86: ...send event to Account 1 but is unsuccessful N Account 1 Account 2 Step 3 Panel keeps trying to send event to Account 1 until the programmed Number Of Attempts has been reached Step 4 Panel switches to Account 2 and successfully transmits the event Y Account 1 Account 2 Done Note The same sequence of events would happen if Account 2 was set to Must Report firealarmresources com ...

Page 87: ...ff premise signal transmission for ULC When using these alarm communicators the DACT shall be configured for Contact ID When configuring the dialers the Dialer Group Number needs to be programmed to match the actuated Zone Number Refer to the Alarm Communicator Installation Instruction for compatible receivers For US installations wiring between the DACT and the alarm communicator shall be within ...

Page 88: ...83 WIRING DIAGRAM FOR DSC S TL300CF AND LE4010CF CONNECTION INCLUDING TROUBLE REPORTING ROUTE firealarmresources com ...

Page 89: ...84 LE4010 CF Configuration Reference from DSC Installation Manual firealarmresources com ...

Page 90: ...85 TL300 CF Configuration Reference from DSC Installation Manual firealarmresources com ...

Page 91: ... connected to Input 1 of the transmitter and transmission delay is to be configured via CONNECT 24 The LBT and TEST shall be connected to FACP s trouble inputs The outputs are active low switched to ground and shall be connected via listed supervision relay suggested model DSC RM 2 or RM1C firealarmresources com ...

Page 92: ...irst hour after a panel startup the panel will check the detector chamber values every 10 minutes After that the panel will check the chamber reading every 24 hours If the panel detects the detector is a little dirty than before it would send a compensation value to detector If a panel has detected that a detector has reached the upper limit of compensation the panel reports a dirty trouble Otherw...

Page 93: ...Check default Manual release takes effect even when abort is activated Uncheck Manual release doesn t take effect when abort is activated but it takes effect immediately when the abort is deactivated Manual release switch is not self restoring Users need to press the Reset button on the panel to restore the manual release switch Abort Pause the countdown time or re time 60 s Physical Disconnect Sw...

Page 94: ...lease Trouble Indication Users can select either one as needed Each Area corresponds to one LED zone on the annunciator Area 1 corresponds to zone 1 Area 2 corresponds to zone 2 etc By selecting Normal or Release Trouble Indication users get different LED status and different meaning the LEDs represent In this case Area 1 is set to Release Trouble Indication and Area 2 is set to Normal Area Functi...

Page 95: ...se circuit trouble Yellow steady Releasing circuit trouble Off Releasing circuit is normal 2 Invalid abort trouble Yellow steady Abort switch activation normal standby condition Off No invalid abort switch activation firealarmresources com ...

Page 96: ...after a preset period of time Class A Circuit An initiating device or notification appliance circuit within which all components remain fully functional even though a single open or ground exists in the circuit Class B Circuit An initiating device or notification appliance circuit within which some or all components may be disabled with a single open exists in the circuit Detector FirePrint An int...

Page 97: ...listing states either that the equipment or material meets appropriate standards or has been tested and found suitable for use in a specified manner NEC National Electrical Code also published as NFPA standard 70 Notification Appliance An electrically operated appliance used to indicate the system status such as a bell horn strobe light or speaker Notification Appliance Circuit NAC A circuit to wh...

Page 98: ...ed that any flow of water from a sprinkler system equal to or greater than that from a single automatic sprinkler head will result in activation of this switch and subsequent indication of an alarm condition Zone A designated area of a building Commonly zone is interchanged with initiating device circuit Serial interface circuit Circuit connect to annunciator RPM FCA2018 U1 Signaling line circuit ...

Page 99: ...94 APPENDIX N PAD 4 WIRING INSTRUCTION Placeholder for PAD 4 to FC360 wiring instruction so the PAD 4 is able to report troubles back to the FC360 firealarmresources com ...

Page 100: ...pport checkbox should be ticked as True In the auto configuration mode the Isolator Support checkbox is ticked as true automatically when the device is wired as an isolator module Separate isolator modules and isolators on devices can t be used on the same circuit otherwise the system reports trouble If separate isolator modules are used the devices with isolators must be wired as non isolator mod...