69
Communication Port Connector
The communication port is connected to the USB port
of the computer that has the FXS901-U2
programming tool. This is used to upload and/or download panel configuration if this method of
programming is used.
The computer must be disconnected from the panel if not in use.
LEDS, Buzzer and Dedicated Push Buttons
The LEDs operate as follows:
Item
LED
Color
Status
Description
1
Alarm
Red
Steady ON
There are alarm events, and all alarm events
have been acknowledged.
OFF
There is no alarm event in system.
Flashing
There are alarm events in system, but some of
them have not been acknowledged.
2
Power
(US)
Power On
(Canada)
Green
Steady ON
The system's power works normally. Both the
main power and battery are in normal status.
OFF
The system is not powered on. This LED can
be OFF only when the system is shut down.
Flashing
The main power is in trouble and system is
powered via battery.
3
Silenced
(US)
Signal
Silence
(Canada)
Yellow
Steady ON
All outputs which can be silenced are silenced.
OFF
There are no silenced outputs in system.
Flashing
Both silenced and unsilenced outputs exist.
4
Trouble
Yellow
Steady ON
There are trouble events, and all of them have
been acknowledged.
OFF
There is no trouble event in system.
Flashing
There are trouble events in system, but some
of them have not been acknowledged.
5
Supervisory
Yellow
Steady ON
There are supervisory events, and all of them
have been acknowledged.
OFF
There is no supervisory event in system.
Flashing
There are supervisory events in system, but
some of them have not been acknowledged.
6
Ground Fault
Yellow
Steady ON
There are Ground Fault events in system.
firealarmresources.com
Summary of Contents for FC2005
Page 5: ...firealarmresources com ...
Page 33: ...28 FC2005 Enclosure Mounting Pictures firealarmresources com ...
Page 48: ...43 firealarmresources com ...
Page 58: ...53 This page is left intentionally blank firealarmresources com ...
Page 89: ...84 LE4010 CF Configuration Reference from DSC Installation Manual firealarmresources com ...
Page 90: ...85 TL300 CF Configuration Reference from DSC Installation Manual firealarmresources com ...