APPENDIX
-
L: RELEASING OPERATION
Configure:
•
Set up a countdown time for the releasing operation to start when the releasing control
condition is satisfied.
•
Set up the activation time for the NAC/Output channel:
ReleaseSync: operate simultaneously with the releasing channel.
Immediately: operate once the releasing control condition is satisfied.
•
When the releasing control condition is satisfied, the countdown time starts. When the
countdown time is over, the releasing operation starts to distinguish the fire.
Manual releasing:
•
When the releasing control is in pre-discharge phase, the releasing circuit is activated
immediately when the corresponding manual release is triggered.
•
When the releasing control is not in the pre-discharge phase, a countdown timer of the
releasing circuit starts when the corresponding manual release is triggered. The
countdown time can be customized and the range is 10
…
60 s. UL allows up to 30
seconds.
•
Checkbox:
“
Manual release overrides abort
”
.
Check (default)
—
Manual release takes effect even when abort is activated
Uncheck
—
Manual release
doesn’t
take effect when abort is activated, but it takes effect
immediately when the abort is deactivated.
•
Manual release switch is not self-restoring. Users need to press the
“
Reset
”
button on
the panel to restore the manual release switch.
Abort
•
Pause the countdown time or re-time 60 s.
Physical Disconnect Switch
Releasing service fire alarm systems used for fire
suppression-releasing service (non-water
based) shall have the capability to disconnect releasing circuit(s).
A Listed physical disconnect switch (such as Fike model 10-2705) shall be used.
To provide a separate releasing notification, Audible Base (ABHW) needs to be installed
and programmed to sound March tone during pre-discharge, and a different tone (e.g.
continuous tone) when it discharges.
For Canadian Releasing applications the AW-3B self-restoring abort switch must be used.
It is painted blue and contains French Canadian verbiage.
For Canadian Releasing applications, the MSM-RB non-self-restoring manual release
switch must be used. It is painted yellow and contains French Canadian verbiage.
firealarmresources.com
Summary of Contents for FC2005
Page 5: ...firealarmresources com ...
Page 33: ...28 FC2005 Enclosure Mounting Pictures firealarmresources com ...
Page 48: ...43 firealarmresources com ...
Page 58: ...53 This page is left intentionally blank firealarmresources com ...
Page 89: ...84 LE4010 CF Configuration Reference from DSC Installation Manual firealarmresources com ...
Page 90: ...85 TL300 CF Configuration Reference from DSC Installation Manual firealarmresources com ...