57
Smart Infrastructure
A6V10393190_h_en_--
2019-09-01
7.1.3
Input
Configure the input parameters.
Select an input for programming.
Class change signal
Activate all sounder controls as long as the input is closed.
Dependency reset
Reset function is suppressed if the Alarm dialer is activated or if ACK
is not pressed before.
Level 2 access
Enables the access level 2 as long as the input is closed.
Disable dialer outputs
Disable fault and Alarm dialer as long as the input is closed.
Manned / unmanned
Switch to manned as long as the input is closed.
Toggle manned /
unmanned
Toggle between manned / unmanned if the signal change on the input.
External PSU fault
Activate fault condition from the external PSU fault as long as the
input is closed.
Alarm dialer fault
Activate general fault and LED 'Alarm dialer fault' until reset.
Application remote transmission device is in fault state.
Dialer device
confirmation signal
Generate an event of 'Fire brigade is called' and is used to activate
outputs and the LED 'Fire brigade is called' as long as the input is
closed.
Activate alert mode
This mode (alert) supports that the output(s) is activated as long as
the input is closed.
Menu: Configure
g
Outputs
g
Activation condition
g
Alert by ext. input
ACK
Acknowledge all events if the input is activated.
SE ACK function
Acknowledge function is suppressed if the Alarm dialer is activated.
Reset
Reset function is always available independently of the access level.
If the mode 'Class change signal' is selected, you can edit the customer text.
See chapter 7.5.
It is not allowed to configure two or more inputs as 'Class change signal'.
*Customer
text
Mode
Input
1..n
Input