The mixed line allows a mixture of detectors and manual call points within the same
zone. Moreover it can distinguish between direct and delayed alarming.
Technical:
-
Siemens detectors 110-series or detectors with an alarm resistor are required for
delayed alarming (AVC, V1 / V2).
-
MCPs require a Z-diode for direct alarming (AVC).
-
Max. 32 devices on each line.
-
Each line must be terminated with EOL element Transzorb diode (18 V TVS).
Programming:
-
Configure
g
Zone
g
Zone 1 – n
g
Mode
g
Mixed MCP & det.
-
Configure
g
Zone
g
Zone 1 – n
g
AVC
g
Via AVC timer MCP direct
Zone mode 'Mixed' does NOT comply with EN 54-13.
Behavior of MCP in zone coincidence with function 'direct alarming' is not supported.