Standby
[mA]
Alarm
[mA]
Standby
[mA]
Alarm
[mA]
FC122-ZA
4 zone panel
54
123
Out 1 (e.g. Sounders)
Out 2 (e.g. Sounders)
Aux. output
Accessory cards
FCA1203-Z1
(1st)
Output card 2M 2R
12
25
Out A&B (e.g. Sounders)
FTO1203-H1
EVAC Module
0.5
2.2
Standby current [A]
Alarm current [A]
If the total current of the outputs (Sounders, etc.) is higher than
500mA
, then an external
power supply is required.
In order to reduce the total current:
-
Power the output A&B from the external power supply (possible per card).
-
Move the Auxiliary output to the external power supply.
Choose the appropriate battery size depending on the calculated capacity.
[(Standby time × Standby current) + (Alarm time × sum alarm current)] × Aging factor = Capacity (max.12 Ah)
_ _ h
× 0._ _ _ A
+ 0.5 h
× _._ _ _ A
× 1.25
=
Standby time [h]:
24, 30 or 72
Alarm time [h]:
0.5 hour
Aging factor:
1.25
Standby current [A]:
Total current in standby mode
Alarm current [A]:
Total current in alarm mode
Capacity [Ah]:
4.5 Ah; 7 Ah