Device Test
Smoke detector
1.
Enable test mode for the zone.
2.
Place detector tester RE6 or RE8ST on detector head.
3.
Wait until LED is on – Sounder sounds 1 sec.
4.
Remove testing unit -
Automatic reset of test alarm after 15 sec.
5.
Set zone to normal mode operation
.
Heat detector
1.
Enable test mode for the zone.
2.
Place detector tester RE6T or RE7T on detector head
and turn on heater.
3.
Wait until LED is on – Sounder sounds 1 sec.
4.
Remove testing unit -
Automatic reset of test alarm after 15 sec.
5.
Set zone to normal mode operation.
Manual call point
1.
Enable test mode for the zone.
2.
Depending on type of call point, insert test key or
open cover to activate.
3.
Wait until LED is on - Sounder sounds 1 sec.
4.
Remove test key or close door -
Automatic reset of test alarm after 15 sec.
5.
Set zone to normal mode operation.
Detector test for multiple protocol detectors FDOOT241-A9 and FDOOT241-9 in
collective mode
In collective mode, the FDOOT241-A9 and FDOOT241-9 multiple protocol detectors can
only be activated via the command '2.4 ALARM' using the FDUD292 detector exchanger
and tester and the FDUD293 intelligent detector tester.
10.4
Completion work
1.
Activate a test alarm through the system operator with remote transmission.
2.
Disable all 'OFF' status.
3.
Have system owner confirm the revision.