37
Smart Infrastructure
A6V10393190_h_en_--
2019-09-01
5
Function overview
5.1
Operating functions
The operating functions are related to the following topics.
Alarm
Disable / Enable
System test
- Acknowledge
- Reset
- Silence sounder
- Manned / unmanned
- Cancel alarm delay
- Zone
- Sounder control
- Fire output
- Alarm dialer
- Fault dialer
- Mode walk test with
sounder activation for
1 second
- LED test
5.2
Access levels
The FC12x provides four different access levels.
Access
level
Password
Function
1
No need
End user to view pending events.
2
5555
or
key switch
Instructed and authorized end user:
-
Switch on / off zones and outputs.
-
Automatic logout after 2 minutes of no operation.
-
Password is not necessary if a key switch is used.
3
6666
Commissioning personnel:
-
System programming.
-
Automatic logout after 10 minutes of no operation.
-
The basic function of panel will not continue.
4
6666
and front
cover open
Commissioning personnel:
-
Save and restore site configuration.
-
Upload history log.
-
Update firmware.
6669
-
Reset alarm counter.