background image

4/6 

Siemens 

QAX33.1 – Room unit with PPS2 interface 

CA2N1642en_02 

Building Technologies 

 

30 Jun 2009 

Installation notes 

Local installation regulations must be observed. 

The room unit is not protected against connection to AC 230 V.  
 

Commissioning notes 

After an interrupt of the PPS2 interface the communication will only be re-established 
when the connected controller polls the PPS2 addresses. The duration of the corre-
sponding cycle is: 
RXA: 10 sec; RXB, RXL and RXC: 3 min; PX: 30 sec. 

The following routine occurs in the room unit when the power supply is connected (via 
the PPS2 interface) or after a reset via the controller: 

Step Function Description 

LED test 

The LEDs are operated in sequence for 1 s each 

2 Device 

ready 

After a delay of 1 s the device will be ready for PPS2 communi-
cation. The actual control mode is displayed after a further delay 
of 5 s. 

 

Technical data  

 

Supply voltage 

Operating voltage range 

SELV / PELV DC 12 ... 15 V 

 

The room unit receives its power from the connected controller, via the PPS2 interface 

 

Power consumption (from controller) 

Max. 0.10 VA 

Function data 

Temperature sensor 

 

 

Measuring element 

NTC resistor 

 

Measuring range 

0 ... 40 °C 

 Response 

time 

 8 min 

 

Accuracy (5 ... 30 °C) 

 0.5 K 

 Accuracy 

(25 

°C) 

 0.25 K 

 Setpoint 

correction 

 

 

Correction range (determined by controller) max. 

 12 K (default 

 3 K) 

 

Accuracy over full correction range 

10 % 

 

Indication (control mode) 

2 LEDs, yellow 

Interfaces 

Type of interface between controller and  
room unit  

PPS2  
(point-to-point interface, Version 2) 

 

Baud rate 

4.8 kbit/s 

Cable connections 

Connection terminals (screw terminals) 

Stranded or solid conductors   
0.8 ... 2.5 mm

2

 

 

Single cable length controller – Room unit 

See Installation guidelines: 
DESIGO RXC: CA110334,  
DESIGO RXB & RXL: CM110381 
DESIGO RXA: CA2Z3884 
DESIGO PX: CA110396 

 

Cable type 

2-core or 4-core, twisted pairs,  
unscreened  

 

Connecting cable for service tool 

Off-the-shelf, max. 3 m 

Housing protection standard  Protection standard to EN 60529 

IP 30 

Protection class 

Insulation protection class 

III 

 

STOP

  Note! 

Response on start-up 

Summary of Contents for DESIGO RX QAX33.1

Page 1: ...nit is used in rooms controlled by an individual room control system to mea sure the room temperature and for operation of a room controller The QAX33 1 is typi cally used in conjunction with a fan coil system for fan control It can also be used in conjunction with a DESIGO PXC automation station 1 The room unit incorporates a socket for a commissioning and service tool or service terminal This to...

Page 2: ...perature sensor element setpoint adjuster rocker switch for mode selection and fan speed selection plug in connectors and a socket for the commissioning and service tool or service terminal Both the housing and base are made of plastic Base unit Housing 80082 80084 Socket for the commissioning and service tool or service terminal 80168A Dial for stepless adjustment of the setpoint LEDs to indicate...

Page 3: ...e the systems setup for collecting electronic waste Observe all local and applicable laws Engineering notes The device receives its power from the connected controller via the PPS2 interface extra low voltage Only one room unit may be connected to a RX room controller A maximum of 5 room units may be connected to a PXC automation station they are identified by different settings of their address p...

Page 4: ...ge range SELV PELV DC 12 15 V The room unit receives its power from the connected controller via the PPS2 interface Power consumption from controller Max 0 10 VA Function data Temperature sensor Measuring element NTC resistor Measuring range 0 40 C Response time 8 min Accuracy 5 30 C 0 5 K Accuracy 25 C 0 25 K Setpoint correction Correction range determined by controller max 12 K default 3 K Accur...

Page 5: ...Dimensions Color Housing front dial NCS S 0502 G RAL 9003 signal white Housing base unit rocker switch RAL 7035 light grey Weight Excluding packaging 0 12 kg Connection terminals The tool socket on the room unit provides access to the connected individual room controller via the commissioning and service tool or the service terminal The bus cable Terminals 3 and 4 is therefore looped to the tool s...

Page 6: ... RXC room controller 1741A03 PPS2 Tool A R1 B 7 8 1 2 4 3 2 1 C C CP CP N1 CP CP CLA CLB PPS2 LonWorks Bus Twisted pair R1 Room unit QAX33 1 N1 Room controller RXC A Connection for RXT10 commissioning and service tool B Connection for service terminal with PPS2 interface Dimensions 9 5 32 36 4 2 60 80087 90 100 56 60 56 All dimensions in mm 2000 2009 Siemens Switzerland Ltd Subject to change ...

Reviews: