background image

CA2N1642en_02 
30 Jun 2009 

Building Technologies

 

 

1

642

 

 

 

 

 

 

 DESIGO™ 

 

RX 

 

 

Room unit with PPS2 
interface 

QAX33.1

 

for use with:  –  devices of the ranges DESIGO RXC, RXB, RXL, and RXA (PPS2)  
 

–  DESIGO PX Automation stations 

1)

 

 

–  devices with a PPS2 interface 

 

 

 

Room temperature measurement 

 

Room temperature setpoint adjuster 

 

Rocker switch for control mode selection (

 

/ Auto) and manual control of 

the fan in fan-coil systems (up to 3 speeds) 

 

PPS2 interface to controller 

 

Socket for commissioning and service tool or service terminal 

Use 

The room unit is used in rooms controlled by an individual room control system, to mea-
sure the room temperature and for operation of a room controller. The QAX33.1 is typi-
cally used in conjunction with a fan-coil system (for fan control). 

It can also be used in conjunction with a DESIGO PXC… automation station 

1)

The room unit incorporates a socket for a commissioning and service tool or service 
terminal. This tool socket provides access via the PPS2 interface or via a bus system 
(e.g. L

ON

W

ORKS

® bus) to the connected individual room controller.  

 

1)  If room units QAX32.1, QAX33.1, QAX34.1 or QAX84.1 are used in conjunction with a PXC auto-

mation station, the room unit will show the request of the user and not the effective state. 

Summary of Contents for DESIGO RX QAX33.1

Page 1: ...nit is used in rooms controlled by an individual room control system to mea sure the room temperature and for operation of a room controller The QAX33 1 is typi cally used in conjunction with a fan coil system for fan control It can also be used in conjunction with a DESIGO PXC automation station 1 The room unit incorporates a socket for a commissioning and service tool or service terminal This to...

Page 2: ...perature sensor element setpoint adjuster rocker switch for mode selection and fan speed selection plug in connectors and a socket for the commissioning and service tool or service terminal Both the housing and base are made of plastic Base unit Housing 80082 80084 Socket for the commissioning and service tool or service terminal 80168A Dial for stepless adjustment of the setpoint LEDs to indicate...

Page 3: ...e the systems setup for collecting electronic waste Observe all local and applicable laws Engineering notes The device receives its power from the connected controller via the PPS2 interface extra low voltage Only one room unit may be connected to a RX room controller A maximum of 5 room units may be connected to a PXC automation station they are identified by different settings of their address p...

Page 4: ...ge range SELV PELV DC 12 15 V The room unit receives its power from the connected controller via the PPS2 interface Power consumption from controller Max 0 10 VA Function data Temperature sensor Measuring element NTC resistor Measuring range 0 40 C Response time 8 min Accuracy 5 30 C 0 5 K Accuracy 25 C 0 25 K Setpoint correction Correction range determined by controller max 12 K default 3 K Accur...

Page 5: ...Dimensions Color Housing front dial NCS S 0502 G RAL 9003 signal white Housing base unit rocker switch RAL 7035 light grey Weight Excluding packaging 0 12 kg Connection terminals The tool socket on the room unit provides access to the connected individual room controller via the commissioning and service tool or the service terminal The bus cable Terminals 3 and 4 is therefore looped to the tool s...

Page 6: ... RXC room controller 1741A03 PPS2 Tool A R1 B 7 8 1 2 4 3 2 1 C C CP CP N1 CP CP CLA CLB PPS2 LonWorks Bus Twisted pair R1 Room unit QAX33 1 N1 Room controller RXC A Connection for RXT10 commissioning and service tool B Connection for service terminal with PPS2 interface Dimensions 9 5 32 36 4 2 60 80087 90 100 56 60 56 All dimensions in mm 2000 2009 Siemens Switzerland Ltd Subject to change ...

Reviews: