6/6 

Siemens 

QAX33.1 – Room unit with PPS2 interface 

CA2N1642en_02 

Building Technologies 

 

30 Jun 2009 

Connection diagram (Example: RXC) 

The following example shows the room unit connected to a DESIGO RXC room  
controller: 
 

17

41

A

03

PPS2

Tool

A

R1

B

7 8 1 2

4 3 2 1

C–

C+

CP

CP

+

N1

CP

+

CP

CLA

CLB

PPS2

LonWorks® Bus

  

 = Twisted pair 

 
R1 

Room unit QAX33.1 

N1 Room 

controller 

RXC... 

Connection for RXT10 commissioning and service tool 

Connection for service terminal with PPS2 interface 

 
 

Dimensions 

9,

5

32

36

4,2

60

80087

90

10

0

56

60

56

 
 

 

All dimensions in mm 

2000 - 2009 Siemens Switzerland Ltd.

Subject to change

.
.
.

Summary of Contents for DESIGO RX QAX33.1

Page 1: ...nit is used in rooms controlled by an individual room control system to mea sure the room temperature and for operation of a room controller The QAX33 1 is typi cally used in conjunction with a fan coil system for fan control It can also be used in conjunction with a DESIGO PXC automation station 1 The room unit incorporates a socket for a commissioning and service tool or service terminal This to...

Page 2: ...perature sensor element setpoint adjuster rocker switch for mode selection and fan speed selection plug in connectors and a socket for the commissioning and service tool or service terminal Both the housing and base are made of plastic Base unit Housing 80082 80084 Socket for the commissioning and service tool or service terminal 80168A Dial for stepless adjustment of the setpoint LEDs to indicate...

Page 3: ...e the systems setup for collecting electronic waste Observe all local and applicable laws Engineering notes The device receives its power from the connected controller via the PPS2 interface extra low voltage Only one room unit may be connected to a RX room controller A maximum of 5 room units may be connected to a PXC automation station they are identified by different settings of their address p...

Page 4: ...ge range SELV PELV DC 12 15 V The room unit receives its power from the connected controller via the PPS2 interface Power consumption from controller Max 0 10 VA Function data Temperature sensor Measuring element NTC resistor Measuring range 0 40 C Response time 8 min Accuracy 5 30 C 0 5 K Accuracy 25 C 0 25 K Setpoint correction Correction range determined by controller max 12 K default 3 K Accur...

Page 5: ...Dimensions Color Housing front dial NCS S 0502 G RAL 9003 signal white Housing base unit rocker switch RAL 7035 light grey Weight Excluding packaging 0 12 kg Connection terminals The tool socket on the room unit provides access to the connected individual room controller via the commissioning and service tool or the service terminal The bus cable Terminals 3 and 4 is therefore looped to the tool s...

Page 6: ... RXC room controller 1741A03 PPS2 Tool A R1 B 7 8 1 2 4 3 2 1 C C CP CP N1 CP CP CLA CLB PPS2 LonWorks Bus Twisted pair R1 Room unit QAX33 1 N1 Room controller RXC A Connection for RXT10 commissioning and service tool B Connection for service terminal with PPS2 interface Dimensions 9 5 32 36 4 2 60 80087 90 100 56 60 56 All dimensions in mm 2000 2009 Siemens Switzerland Ltd Subject to change ...

Reviews: