3/6 

Siemens 

QAX33.1 – Room unit with PPS2 interface 

CA2N1642en_02 

Building Technologies 

 

30 Jun 2009 

Position Fan 

control 

1)

 Control 

mode 

1)

 

 

Fan controlled automati-
cally by controller  

The controller operates at the “setback” 
setpoints (at night, or when room is un-
occupied or occupied intermittently)  

Auto 

Fan controlled automati-
cally by controller 

Comfort mode (room occupied) 

 

Manual, fan speed 1 

 

 

Manual, fan speed 2 

 

 

Manual, fan speed 3 

 

1) 

For details of these functions, refer to the application description for the relevant controller range.  
 
 

01884

 

 
 
 
 
 
Address plugs inside the housing 
They allow setting the address in cases where several 
room units are connected to one controller. 
The room units are delivered with address 1. 

Disposal 

 

The device is classified as waste electronic equipment in terms of the European Direc-
tive 2002/96/EC (WEEE) and should not be disposed of as unsorted municipal waste. 
The relevant national legal rules are to be adhered to.  
Regarding disposal, use the systems setup for collecting electronic waste. 
Observe all local and applicable laws. 

Engineering notes 

The device receives its power from the connected controller via the PPS2 interface 
(extra low voltage).

 

Only one room unit may be connected to a RX… room controller.  

A maximum of 5 room units may be connected to a PXC… automation station (they are 
identified by different settings of their address plugs) 

A twisted-pair cable is required for the connection to the controller.  
DESIGO RX uses four-core cables, DESIGO PX uses two-core cables (see the respec-
tive installation guides). Screening is not required. 

Mounting 

 

The room unit is suitable for wall-mounting and for mounting on a recessed conduit 
box.  

 

Do not mount in recesses, shelves, behind curtains or doors, or above or near heat 
sources. 

 

Avoid exposure to direct sunlight or draughts.  

 

The electrical wiring conduit must be sealed where it joins the room unit, to prevent 
the occurrence of draughts in the conduit which could affect the sensor. 

 

The specified ambient conditions must be complied with.  

 

Mounting instructions are printed on the room unit packaging.  

 

A mounting kit is included with the unit. 

Address plugs 

Summary of Contents for DESIGO RX QAX33.1

Page 1: ...nit is used in rooms controlled by an individual room control system to mea sure the room temperature and for operation of a room controller The QAX33 1 is typi cally used in conjunction with a fan coil system for fan control It can also be used in conjunction with a DESIGO PXC automation station 1 The room unit incorporates a socket for a commissioning and service tool or service terminal This to...

Page 2: ...perature sensor element setpoint adjuster rocker switch for mode selection and fan speed selection plug in connectors and a socket for the commissioning and service tool or service terminal Both the housing and base are made of plastic Base unit Housing 80082 80084 Socket for the commissioning and service tool or service terminal 80168A Dial for stepless adjustment of the setpoint LEDs to indicate...

Page 3: ...e the systems setup for collecting electronic waste Observe all local and applicable laws Engineering notes The device receives its power from the connected controller via the PPS2 interface extra low voltage Only one room unit may be connected to a RX room controller A maximum of 5 room units may be connected to a PXC automation station they are identified by different settings of their address p...

Page 4: ...ge range SELV PELV DC 12 15 V The room unit receives its power from the connected controller via the PPS2 interface Power consumption from controller Max 0 10 VA Function data Temperature sensor Measuring element NTC resistor Measuring range 0 40 C Response time 8 min Accuracy 5 30 C 0 5 K Accuracy 25 C 0 25 K Setpoint correction Correction range determined by controller max 12 K default 3 K Accur...

Page 5: ...Dimensions Color Housing front dial NCS S 0502 G RAL 9003 signal white Housing base unit rocker switch RAL 7035 light grey Weight Excluding packaging 0 12 kg Connection terminals The tool socket on the room unit provides access to the connected individual room controller via the commissioning and service tool or the service terminal The bus cable Terminals 3 and 4 is therefore looped to the tool s...

Page 6: ... RXC room controller 1741A03 PPS2 Tool A R1 B 7 8 1 2 4 3 2 1 C C CP CP N1 CP CP CLA CLB PPS2 LonWorks Bus Twisted pair R1 Room unit QAX33 1 N1 Room controller RXC A Connection for RXT10 commissioning and service tool B Connection for service terminal with PPS2 interface Dimensions 9 5 32 36 4 2 60 80087 90 100 56 60 56 All dimensions in mm 2000 2009 Siemens Switzerland Ltd Subject to change ...

Reviews: