s
Operating manual
24
TSP~
Plausibility
threshold **
For ATD function, see Chap. 15.2.4
MEM.T
Hold time for Min/Max
Hold time in sec.
FIL.M
Smoothing filter for
min/max*
OFF
OFF
ON
ON
FIL.T
Smoothing time*
Time t98 in sec.
END
End
Exit menu
*
Only available with Min/Max and Double Max modes
**
Only available with ATD function
16.1.2 Temperature measurement lambda 1
(Configuration layer:
C002
)
In the factory default configuration, all parameter settings for digital in-
puts and outputs will be hidden.
Parameter Function
Explanation
E.TB.1
Array size
Use array with 1-10 entries or enter material
constant directly into the pyrometer
EPS.1
Emissivity factor L1
Enter material constant directly into the py-
rometer
E.IDX
Memory position
Choose an entry from the material constants
array
E. 01
Assign material
constants
Customize the array; assign a value to each
of the material constants in the array. Possible
indexes depend on the size of the array
TAU.1
Transmittance factor
L1
BAC.1
Ambient temperature
compensation
BAC.T
Temp. of ambient
source of radiation
BAC.%
Influence of ambient
IR radiation
The reflected thermal radiation from the sur-
roundings as a portion of the total IR radiation
collected by the sensor in %
LIN.1
Temperature offset
using linear
OFF
off
2-10
number of nodes used
L. X1
node x 1 - 10
Signal input (initial value) node n
L. Y1
node y 1 - 10
Signal output (resulting value) node n
FIL.1
Smoothing filter
OFF
smoothing not activated
ON
simple smoothing
FIL.T
Smoothing time
time t98 in sec for simple smoothing
MEM.1
Min/Max memory
OFF
off
MIN
lowest (min.)temperature, single
MAX
highest (max.) temperature, single
DBL.M
double maximum
DIS.M
ATD function
MEM.T
Hold time for Min/Max
Hold time in sec.
FIL.M
Smoothing filter for
min/max*
OFF
OFF
ON
ON
FIL.T
Smoothing time*
Time t98 in sec.
Summary of Contents for Ardoptix PT 140 AF1
Page 1: ...Two colour Pyrometer PT 14x 7MC3040 Operating Manual 03 2017 ...
Page 2: ......
Page 3: ...Two colour Pyrometer PT Ident Nr 106 7393 PT14x_si_en doc Stand 21 03 2017 830 hm 810 het ...
Page 8: ...s Operating manual ...
Page 56: ...s Operating manual 48 29 Dimensions ...
Page 63: ...s Operating manual 55 ...
Page 64: ......
Page 65: ......
Page 66: ......
Page 67: ......