Chapter 4 - 7SR157 · Data Communications Definitions
© 2016 Siemens Protection Devices Limited
Chapter 4 - Page 19 of 58
4. MODBUS Definitions
4.1 Introduction
This section describes the MODBUS-RTU protocol implementation in the relays. This protocol is used for
communication with a suitable control system.
This protocol can be set to use any or all of the relays hardware interfaces (USB, Fibre Optic, RS232 and RS485)
where fitted. The relay can communicate simultaneously on all ports regardless of protocol used.
The Station Address of the port being used must be set to a suitable address within the range 1 - 247 to enable
communication. This can be set by the Communications Menu : COM n-xxxxx Station Address setting.
Communication via MODBUS over Ethernet requires external devices. Please refer to the documents TCPIP
Catalogue Sheet and TCPIP Interface Technical Guidance Notes for more information.
Definitions with shaded area are not available on all relay models.
Summary of Contents for 7SR157 Argus
Page 2: ......
Page 4: ...7SR157 Contents ...
Page 58: ...7SR158 Technical Manual Chapter 3 Page 2 of 18 2022 Siemens Protection Devices Limited ...
Page 76: ...7SR157 Technical Manual Chapter 4 Page 2 of 58 2016 Siemens Protection Devices Limited ...
Page 80: ...7SR157 Technical Manual Chapter 4 Page 6 of 58 2016 Siemens Protection Devices Limited ...
Page 92: ...7SR157 Technical Manual Chapter 4 Page 18 of 58 2016 Siemens Protection Devices Limited ...
Page 122: ...7SR157 Technical Manual Chapter 4 Page 48 of 58 2016 Siemens Protection Devices Limited ...
Page 124: ...7SR157 Technical Manual Chapter 4 Page 50 of 58 2016 Siemens Protection Devices Limited ...
Page 126: ...7SR157 Technical Manual Chapter 4 Page 52 of 58 2016 Siemens Protection Devices Limited ...
Page 150: ...7SR157 Technical Manual Chapter 5 Page 18 of 18 2018 Siemens Protection Devices Limited ...
Page 179: ...Siemens Protection Devices 1 ...