6.2
Additional (Optional) Ethernet Connection for IEC 61850
Rear Ethernet Comms port Ch 1 and Ch 2 comprises
Duplex LC 100BaseF in acc. With IEEE802.3
Fibre–
Optic or
RJ45 100BaseT in acc. With IEEE802.3
electrical connectors.
When installing fibre, ensure that the fibres’ bend radii comply with the recommended minimum for the fibre used-
typically 50 mm is acceptable,
62.5/125
µ
m glass fibre with Duplex-LC connector
recommended for all
distances.
To
Control
System
Switch
Ch n
Ch 2
Ch 1
62.5/125
µm
fibre optic
with Duplex LC
connectors or RJ45
electrical connectors
Ch 2
Ch 1
Ch 1
Ch 3
Ch 2
Ch 1
Input
Ch 2
Figure: 6.2-1 Ethernet connection for IEC 61850 (star connection)
Switch
Ch n
Ch 2
Ch 1
Ch 2
Ch 1
Ch 1
Ch 3
Ch 2
Ch 1
Input
To
Control
System
Ch 2
62.5/125
µm
fibre optic
with Duplex LC
connectors or RJ45
electrical connectors
Figure: 6.2-2 Ethernet connection for IEC 61850 (ring connection)
Summary of Contents for 7SR157 Argus
Page 2: ......
Page 4: ...7SR157 Contents ...
Page 58: ...7SR158 Technical Manual Chapter 3 Page 2 of 18 2022 Siemens Protection Devices Limited ...
Page 76: ...7SR157 Technical Manual Chapter 4 Page 2 of 58 2016 Siemens Protection Devices Limited ...
Page 80: ...7SR157 Technical Manual Chapter 4 Page 6 of 58 2016 Siemens Protection Devices Limited ...
Page 92: ...7SR157 Technical Manual Chapter 4 Page 18 of 58 2016 Siemens Protection Devices Limited ...
Page 122: ...7SR157 Technical Manual Chapter 4 Page 48 of 58 2016 Siemens Protection Devices Limited ...
Page 124: ...7SR157 Technical Manual Chapter 4 Page 50 of 58 2016 Siemens Protection Devices Limited ...
Page 126: ...7SR157 Technical Manual Chapter 4 Page 52 of 58 2016 Siemens Protection Devices Limited ...
Page 150: ...7SR157 Technical Manual Chapter 5 Page 18 of 18 2018 Siemens Protection Devices Limited ...
Page 179: ...Siemens Protection Devices 1 ...