AC supply loading
Attribute
VA (RMS)
Voltage
100
110
115
120
200
230
Quiescent Relay (inc. ‘PROT HEALTHY’ LED)
7.5
7.5
7.5
7.5
8
9
Backlight
2
2
2
2
2.1
2.1
Per LED – (Red or Green)
0.06
0.06 0.06
0.06
0.06
0.06
Per LED – Yellow
0.10
0.10
0.10
0.10
0.10
0.10
Per Binary Output
0.6
0.6
0.6
0.6
0.7
0.7
Optional IEC 61850 Comms Interface
5
5
5
5
5.5
5.5
1.2.1.2 Operational Features
Attribute
Value
Comments
0% Dip Withstand Period
50ms
Dip Immunity Acquisition Period
5minutes
Typical time after switch on to
attain claimed immunity to dips
NOTE: Dips in supply that fall below the minimum voltage for a period greater than the
0% Dip With stand Period will invoke a relay reset.
During conditions of auxiliary input voltage variations which are not described (1) in section 1.2.1 and 1.4.3.1,
relays with HV or LV PSU modules may enter a safety protection mode where a power supply shutdown
occurs. This condition is designed to protect the power supply from damage as well as prevent internal relay
faults from developing into dangerous situations.
Once the relay has entered this safety mode, it may be necessary to reduce the auxiliary input voltage to zero
volts for up to 30 seconds before re-application of the auxiliary supply will cause the relay to power up and
operate normally.
(1) Using fuses as on/off switches or allowing batteries to run at very low cell voltages for extended periods
and then attempting to re-charge, are examples of such auxiliary supply conditions.
1.2.2
AC Analogue Voltage
Attribute Nominal
Operating Range
Vn
40 to 160 Vrms
0 to 200 Vrms
Fn
50, 60Hz
47.5 to 52.5Hz and 57.0 to 63.0Hz
1.2.2.1 Burden
Attribute
Value
AC Burden
0.02 VA @ 63.5 V,
≤
0.06 VA @ 110 Vrms
1.2.2.2 Thermal Withstand
Attribute
Value
Overvoltage Withstand (Continuous)
300 Vrms
Summary of Contents for 7SR157 Argus
Page 2: ......
Page 4: ...7SR157 Contents ...
Page 58: ...7SR158 Technical Manual Chapter 3 Page 2 of 18 2022 Siemens Protection Devices Limited ...
Page 76: ...7SR157 Technical Manual Chapter 4 Page 2 of 58 2016 Siemens Protection Devices Limited ...
Page 80: ...7SR157 Technical Manual Chapter 4 Page 6 of 58 2016 Siemens Protection Devices Limited ...
Page 92: ...7SR157 Technical Manual Chapter 4 Page 18 of 58 2016 Siemens Protection Devices Limited ...
Page 122: ...7SR157 Technical Manual Chapter 4 Page 48 of 58 2016 Siemens Protection Devices Limited ...
Page 124: ...7SR157 Technical Manual Chapter 4 Page 50 of 58 2016 Siemens Protection Devices Limited ...
Page 126: ...7SR157 Technical Manual Chapter 4 Page 52 of 58 2016 Siemens Protection Devices Limited ...
Page 150: ...7SR157 Technical Manual Chapter 5 Page 18 of 18 2018 Siemens Protection Devices Limited ...
Page 179: ...Siemens Protection Devices 1 ...