Functional performance
1.3.1
Instrumentation
Instrument Value
Reference
Typical accuracy
V
Voltage
0.1 x Vn
≤
V
≤
1.2 x Vn
1 % Vn
F
Frequency
F = 47.5 to 52.5Hz @ 50Hz
and 57 to 63Hz @60Hz
± 10mHz
1.3.2
Data Communication
1.3.2.1 USB 2.0 Data Communication Interface
Attribute
Value
Physical layer
Electrical
Connectors
USB-Type B
1.3.2.2 RS485 Data Communication Interface
Attribute
Value
Physical layer
Electrical
Connectors
4mm Ring Crimp
1.3.2.3 Fibre Optic Ethernet Data Communication Interface (IEC 61850 Option)
Attribute
Value
Physical layer
Fibre-optic
Connectors
Duplex LC 100BaseF in acc. With IEEE802.3
Recommended fibre
62.5/125
m glass fibre with Duplex-LC connector
Transmission Speed
100 MBits/s
Optical Wavelength
1300 nm
Bridgeable distance
2 km
1.3.2.4 Electrical Ethernet Data Communication Interface (IEC 61850 Option)
Attribute
Value
Physical layer
Electrical
Connectors
RJ45 100BaseT in acc. With IEEE802.3
Transmission Speed
100 MBits/s
Test Voltage (with regard to socket)
500 VAC 50 Hz
Bridgeable distance
20 m
1.3.3
Real Time Clock
The specification below applies only while no external synchronisation signal (e.g. 60870-5-103) is being
received.
Attribute
Value
Accuracy (-10 to +55
o
C)
3.5 ppm (no auxiliary supply connected)
100 ppm (auxiliary supply connected)
Summary of Contents for 7SR157 Argus
Page 2: ......
Page 4: ...7SR157 Contents ...
Page 58: ...7SR158 Technical Manual Chapter 3 Page 2 of 18 2022 Siemens Protection Devices Limited ...
Page 76: ...7SR157 Technical Manual Chapter 4 Page 2 of 58 2016 Siemens Protection Devices Limited ...
Page 80: ...7SR157 Technical Manual Chapter 4 Page 6 of 58 2016 Siemens Protection Devices Limited ...
Page 92: ...7SR157 Technical Manual Chapter 4 Page 18 of 58 2016 Siemens Protection Devices Limited ...
Page 122: ...7SR157 Technical Manual Chapter 4 Page 48 of 58 2016 Siemens Protection Devices Limited ...
Page 124: ...7SR157 Technical Manual Chapter 4 Page 50 of 58 2016 Siemens Protection Devices Limited ...
Page 126: ...7SR157 Technical Manual Chapter 4 Page 52 of 58 2016 Siemens Protection Devices Limited ...
Page 150: ...7SR157 Technical Manual Chapter 5 Page 18 of 18 2018 Siemens Protection Devices Limited ...
Page 179: ...Siemens Protection Devices 1 ...