Chapter 4 - 7SR157 · Data Communications Definitions
© 2016 Siemens Protection Devices Limited
Chapter 4 - Page 37 of 58
OBJECT
REQUEST
(Library will parse)
RESPONSE
(Library will respond with)
Object
Number
Variation
Description
Function Codes
(dec)
Qualifier Codes
(hex)
Function
Codes
(dec)
Qualifier Codes
(hex)
17, 27, 28 (index)
2 (write)
00, 01 (start-stop)
07, 08 (limited qty)
17, 27, 28 (index)
50
0
Time and Date
1 (read)
07, 08 (limited qty)
129
(response)
07 (limited qty = 1)
50
1 (default -
see note 1)
Time and Date
2 (write)
00, 01 (start-stop)
07, 08 (limited qty)
17, 27, 28 (index)
50
3
Time and Date Last
Recorded Time
2 (write)
07 (limited qty)
51
1
Time and Date CTO
129
(response)
130
(unsol. resp)
(limited qty = 1)
51
2
Unsynchronized
Time and Date CTO
129
(response)
130
(unsol. resp)
(limited qty = 1)
52
1
Time Delay Coarse
129
(response)
(limited qty = 1)
52
2
Time Delay Fine
129
(response)
(limited qty = 1)
60
0
Not Defined
60
1
Class 0 Data
1 (read)
06 (no range, or all)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
60
2
Class 1 Data
20 (enbl. unsol.)
21 (dab. unsol.)
22 (assign class)
06 (no range, or all)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
60
3
Class 2 Data
20 (enbl. unsol.)
21 (dab. unsol.)
22 (assign class)
06 (no range, or all)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
60
4
Class 3 Data
20 (enbl. unsol.)
21 (dab. unsol.)
22 (assign class)
06 (no range, or all)
1 (read)
00, 01 (start-stop)
129
(response)
00, 01 (start-stop)
80
1
Internal Indications
2 (write)(see note 3)
00 (start-
stop) index=7
No Object
(function code only)
13 (cold restart)
No Object
(function code only)
14 (warm restart)
No Object
(function code only)
23 (delay meas.)
No Object
(function code only)
24 (record
current time)
Note 1: A Default variation refers to the variation responded when variation 0 is requested and/or in class 0, 1, 2, or
3 scans. Default variations are configurable; however, default settings for the configuration parameters are indicated
in the table above.
Note 2: For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a request is sent with
qualifiers 17 or 28, respectively. Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be
responded with qualifiers 00 or 01. (For change-event objects, qualifiers 17 or 28 are always responded.)
Note 3: Writes of Internal Indications are only supported for index 7 (Restart IIN1-7).
Summary of Contents for 7SR157 Argus
Page 2: ......
Page 4: ...7SR157 Contents ...
Page 58: ...7SR158 Technical Manual Chapter 3 Page 2 of 18 2022 Siemens Protection Devices Limited ...
Page 76: ...7SR157 Technical Manual Chapter 4 Page 2 of 58 2016 Siemens Protection Devices Limited ...
Page 80: ...7SR157 Technical Manual Chapter 4 Page 6 of 58 2016 Siemens Protection Devices Limited ...
Page 92: ...7SR157 Technical Manual Chapter 4 Page 18 of 58 2016 Siemens Protection Devices Limited ...
Page 122: ...7SR157 Technical Manual Chapter 4 Page 48 of 58 2016 Siemens Protection Devices Limited ...
Page 124: ...7SR157 Technical Manual Chapter 4 Page 50 of 58 2016 Siemens Protection Devices Limited ...
Page 126: ...7SR157 Technical Manual Chapter 4 Page 52 of 58 2016 Siemens Protection Devices Limited ...
Page 150: ...7SR157 Technical Manual Chapter 5 Page 18 of 18 2018 Siemens Protection Devices Limited ...
Page 179: ...Siemens Protection Devices 1 ...