7SG164 Ohmega 400 Series Performance Specification
240A
for 2 sec
625A
for 1 cycle (Peak)
AC Voltage Inputs
3.5Vn Continuous
8.15 Burdens
Current Circuits
AC Burden (VA per phase)
1A tap
0.025
2A tap
0.1
5A tap
0.625
Voltage Circuits
0.01VA per phase
NB. Burdens and impedances are measured at nominal rating.
D.C. Burden
DC Burden (watts)
Quiescent (Typical)
15
Max 27
9
Output contact performance
Contact rating to IEC 60255-0-2.
Carry continuously
5A ac or dc
Make and Carry
(limit L/R
≤
40ms and V
≤
300 volts)
for 0.5 sec
20A ac or dc
for 0.2 sec
30A ac or dc
Break
(limit
≤
5A or
≤
300 volts)
ac resistive
1250VA
ac inductive
250VA @ PF
≤
0.4
dc resistive
75W
dc inductive
30W @ L/R
≤
40 ms
50W @ L/R
≤
10 ms
Minimum number of operations
1000 at maximum load
Minimum recommended load
0.5W, limits 10mA or 5V
10
Auxiliary energizing quantity
DC Power Supply
Nominal
Operating
Range
VAUX
30/34V
24V to 37.5V dc
VAUX
50/110/125V
37.5V to 137.5V dc
VAUX
220/250/260V
175V to 286V dc
DC Status Inputs
Nominal Voltage
Operating Range
30/34
18V to 37.5V
48/54
37.5V to 60V
110/125
87.5V to 137.5V
220/250
175 to 286V
Status Input Performance (30V and 48V)
Minimum DC current for operation
10mA
©2011 Siemens Protection Devices Limited
Chapter 5 Page 9 of 13