7SG1641 Ohmega 402 60 Diagrams
4 Distance Protection
Trip Outputs
SOTFTRIP
SOLOTRIP
TRIP3PHASE
AIDEDTRIP
story now in page properties.
hmega 402 Tripping Logic
615S81133 Revision 5
en Nickerson
1
1
BACKUPTRIP
Z2D
1
Z3D
Z4D
ZONE2
ZONE3
ZONE4
&
ENABLEZ4TRIP
Z2G
&
Z2OVERRIDE
ZONE2OVERRIDE
HISET
HSOCC
HSOCA
HSOCB
1
STUBPROTECTION
STUB_C
STUB_A
STUB_B
1
ZONE1
Z1D
Z2G
ZONE2START
Z3G
ZONE3START
Z4G
ZONE4START
Z1G
ZONE1START
HISET
Marshall the highset operations for output/flagging (primary trip operation)
Marshall the stub protection operations for output/flagging (backup trip operation)
Marshall the primary trip sources
Marshall the backup trip sources. In addition to TRIP3PHASE,
these w ill also generate the DAR Lockout (BACKUPTRIP) signal
Generate a general Zone 1 output for alarm and flagging
Generate zone starter signals from the instantaneous zone operations
Zone 2 Override is Zone 2 Inst plus
an external enable signal.
ZONE4TRIP
BACKUPTRIPFLAG
LATCHLOCKOUT
LockoutLatch
S
R
Q
BACKUPTRIPFLAG
1
©2011 Siemens Protection Devices Limited
Chapter 11 Page 6 of 18