7SG1641 Ohmega 402 60 Relay Settings
©2013 Siemens Protection Devices Limited
Chapter 4 Page 12 of 20
Z4 PF Time Delay
(0..10000)
0
ms
An independent time delay from 0 – 10s can be applied to the Zone 4 phase-fault protection elements.
Z4 Earth Fault
(Disabled..Enabled)
Enabled
Operation of the Zone 4 earth-fault elements A-E, B-E & C-E, can be disabled from this setting.
Z4 EF Impedance
(0.1..250)
8
ohms
Defines the Zone 4 earth-fault impedance reach (in terms of secondary positive sequence impedance) for the
mho characteristic.
Z4 EF Time Delay
(0..10000)
0
ms
An independent time delay from 0 – 10s can be applied to the Zone 4 earth-fault protection elements.
2.3 Power Swing Menu
Settings for the power swing element are defined in this section.
Power Swing Detector
(DISABLE..ENABLE)
ENABLE
This setting allows the Power Swing detector to be enabled or disabled.
PSD Zone blocking
(4 Bit Binary)
-111
This defines which Zones of protection tripping would be blocked for in the event of a Power Swing.
PSD Shape
(CIRCULAR..RECTANGULAR)
CIRCULAR
Allows setting of the Power Swing Zone characteristics as either circular or rectangular.
PSD Blinders
(DISABLE..ENABLE)
DISABLE
This allows blinders to be applied to the Power Swing Zone to prevent load encroachment. These are applied
parallel to the line angle when enabled.
PSD Inner Fwd Impedance
(0.1..250)
24
ohms
Sets the inner impedance reach in the forward direction (on the line angle) for the PSD characteristic. This is
usually set equal to, or greater than, the Zone 3 reach.
PSD Inner Rev Impedance
(0.1..250)
8
ohms
Sets the inner impedance reach in the reverse direction (on the line angle) for the PSD characteristic. This is
usually set equal to, or greater than, the Zone 3 reverse reach.
PSD Inner Fwd Blinder
(0.1..250)
16
ohms
This is the impedance (perpendicular to the line angle) between the line impedance and the blinder applied to the
PSD Zone, to the right of the line characteristic. The blinder is applied parallel to the line angle.
PSD Inner Rev Blinder
(0.1..250)
16
ohms
This is the impedance (perpendicular to the line angle) between the line impedance and the blinder applied to the
PSD Zone, to the left of the characteristic. The blinder is applied parallel to the line angle.
PSD Outer Multiplier
(1.05..2) 1.5
x
The outer reach of the Power Swing detector is set as a multiple of the inner reach, normally 1.5 times the inner
reach.
PSD Transit Time
(0..1000)
50
ms
This is the length of time for which the impedance characteristic must be between the inner and outer Zones of
the Power Swing Detector for a Power Swing to be detected. The default setting of 50ms should be suitable for
most applications.