7SG16 Ohmega 402 60 Commissioning
2.2 Output Relays
This test checks that the output relays are functioning correctly. The output relays should be energised in turn and
the contacts should be checked for correct operation using a continuity tester. The output relays can be energised
in a number of ways. The following is the recommended method:
Assign each output relay in turn to ‘Relay Healthy’ in the output relay menu. On pressing the ENTER key the
output relay selected will be energised. Check with a continuity tester that the actual contacts have operated. De-
select the output relay and check that the contact returns. Consult the schematic diagram or Relay Connections
Diagram in the Technical Manual for terminal numbers.
Output Relay
Type
Relay 1-3
Change Over
Relay 4+
Normally Open
OUTPUT CHECKED
NOTES
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
Note: when finished testing the output relays make sure that the ‘Relay healthy’ is re-assigned to the correct
output relay given in the settings file.
OK
Checked
©2010 Siemens Protection Devices Limited
Chapter 9 Page 5 of 19