7SG11 Argus Technical Reference
©2013 Siemens Protection Devices Limited
P20007 Page 41 of 71
Setting name
Range (
bold
= default)
Units Notes
Gn P/F [E/F][SEF] Reclose DTL
2
as Reclose DTL 1
sec
Gn P/F [E/F][SEF] Protection
Trip 3
INST,
DELAYED
Gn P/F [E/F][SEF] Reclose DTL
3
as Reclose DTL 1
sec
Gn P/F [E/F][SEF] Protection
Trip 4
INST,
DELAYED
Gn P/F [E/F][SEF] Reclose DTL
4
as Reclose DTL 1
sec
Gn P/F [E/F][SEF] Shots To
Lockout
1, 2, 3,
4
For 4 reclose shots, 5 trips are
issued – the fifth trip is always
delayed.
Gn P/F [E/F] HS1 Trips to
Lockout
1, 2, 3, 4,
5
Gn P/F [E/F] HS2 Trips to
Lockout
1, 2, 3, 4,
5
Not applicable to SEF sequence
Reclaim Time
0.20, 0.21…
2.0
, 2.1…20,21…
300, 360…3600, 3900…14400
sec
Common setting across all
Groups
applies to all Sequences
Close Pulse
1.0, 1.1…
2.0
…10.0
sec
Common setting across all
Groups
Manual Close Delay
OFF
, 1, 2, 3, 4, 5, 6, 7, 8, 9, 10
sec
Common setting across all
Groups
LO Recovery
as ‘Reclaim Time’
sec
Common setting across all
Groups