7SG11 Argus Technical Reference
©2013 Siemens Protection Devices Limited
P20007 Page 7 of 71
See appropriate case outline and panel drilling drawing, as specified in Diagrams and Parameters document, for
complete dimensional specifications.
Weights
Parameter
Value
Argus 1, E4 case
3.3 kg
Argus 1, E6 case
4.8 kg
Argus 2, E4 case
3.3 kg
Argus 2, E8 case
6.6 kg
Argus 4, E6 case
4.8 kg
Net weight
Argus 6, E8 case
6.6 kg
1.2 Energising Quantities
1.2.1 Characteristic Energising Quantities
Parameter
Value
Nominal frequency
50, 60 Hz
1.2.1.1
AC Current
Nominal Current and Measuring Range
Nominal
Measuring Range
Phase and earth
80 x
In
In
1, 5 A
SEF/REF
2 x
In
Note. 1 A and 5 A nominal inputs are user selectable on each model.
Thermal Withstand
Overload Current
Phase and earth
SEF/REF
Overload Period
1A
5A
1A
5A
continuous
3.0 x
In
2.0 x
In
10 minutes
3.5 x
In
5 minutes
4.0 x
In
3 minutes
5.0 x
In
2 minutes
6.0 x
In
3 seconds
57.7
A
202
A
37.5
A
202 A
2 seconds
70.7
A
247
A
46
A
247 A
1 second
100
A
350
A
65
A
350 A
1 cycle
177
A
618
A
115
A
618 A
Burden
Value
Phase and earth
SEF/REF
Attribute
1A
5A
1A
5A
AC Burden
0.05 VA
0.2 VA
0.2 VA
0.4 VA
Impedance
0.05
0.01
0.2