ULTRAMAT 6 / OXYMAT 6 / CALOMAT 6 / ULTRAMAT 23 / OXYMAT 61
Schnittstelle PROFIBUS DP / PA Interface
A5E00054148-03
132
Function Block AI 3 (Analog Input)
cont.
Class
Sl
ot
Index
abs
Ind
ex
rel
Elem
ent
Default
Value
Object
Parameter description
Data Type
Num
ber
Store
(acc. to
profile)
cy
cli
c
re
ad
wri
te
MAND
33
17
0
FSAVE_TYPE
Output / failure behavoir: type of reaction in
case of sensor failure
unsigned8
1
S
x
x
MAND
34
18
0
FSAVE_VALUE
Output / safety default value in case of power
failure
float
1
S
x
x
MAND
35
19
5.0
ALARM_HYS
Output / safety default value in case of power
failure
float
1
S
x
x
MAND
37
21
100.0
HI_HI_LIM
Output / Output limit values / High alarm limit
float
1
S
x
x
MAND
39
23
100.0
HI_LIM
Output / Output limit values / High warning limit float
1
S
x
x
MAND
41
25
0.0
LO_LIM
Output / Output limit values / Low warning limit float
1
S
x
x
MAND
43
27
0.0
LO_LO_LIM
Output / Output limit values / Low alarm limit
float
1
S
x
x
MAND
46
30
HI_HI_ALM
High alarm limit value status
ds39
1
D
x
1
Unacknowledged
Not acknowledged
2
Alarm State
Alarm status
3
Time stamp
Time stamp
4
Subcode
Subcode
5
Value
Value
MAND
47
31
HI_ALM
High warning limit value status
ds39
1
D
x
1
Unacknowledged
Not acknowledged
2
Alarm State
Alarm status
3
Time stamp
Time stamp
4
Subcode
Subcode
5
Value
Value
MAND
48
32
LO_ALM
Low warning limit value status
ds39
1
D
x
1
Unacknowledged
Not acknowledged
2
Alarm State
Alarm status
3
Time stamp
Time stamp
4
Subcode
Subcode
5
Value
Value
MAND
49
33
LO_LO_ALM
Low alarm limit value status
ds39
1
D
x
1
Unacknowledged
Not acknowledged
2
Alarm State
Alarm status
3
Time stamp
Time stamp
4
Subcode
Subcode
5
Value
Value
MAND
50
34
SIMULATE
Output / Simulation: simulation of the
measured value (PRIMARY_VALUE in
Transducer Block
ds50
1
S
x
x
1
0x4b
Simulate-Status
Output / Simulation: simulation status
2
0.0
Simulate_value
Output / Simulation: simulation value
3
0
Simulate_En/Disable
Output / Simulation: simulation enable –
disable. Default disable (0)
OPT
51
35
OUT_UNIT_TEXT
Unit text, valid, if OUT_SCALE.UNIT set to
"textual unit definition" (1995)
visible_string
16
S
x
x
52
36
bis
reserviert von PNO
60
44
VIEW
65
49
VIEW_1
View-Objekt 1 AI
void
4
D
x
1
ST_REV
6
MODE_BLK
7
ALARM_SUM
10
OUT