ULTRAMAT 6 / OXYMAT 6 / CALOMAT 6 / ULTRAMAT 23 / OXYMAT 61
Schnittstelle PROFIBUS DP / PA Interface
A5E00054148-03
126
7.5.4 Physical
Block
Physical Block PB
Class
Sl
ot
Index
abs
Ind
ex
rel
Elem
ent
Default
Value
Object
Parameter description
Data Type
Num
ber
Store
(acc. to
profile)
cy
cli
c
re
ad
wri
te
BLOCK
1
110
0
BLOCK_OBJECT
Block characteristic
ds32
1
C
x
1
250
Reserved
250 = not used
unsigned8
1
2
1
Block Object
Block-Typ (Function)
unsigned8
1
3
5
Parent Class
Parent class: 01 = Input
unsigned8
1
4
250
Class
01 = Analog Input
unsigned8
1
5
0
DD-Reference
reserved
unsigned32
1
6
0
DD-Revision
reserved
unsigned16
1
7
0x4002
Profile
PA-profil-number assigned by PNO for
PROFIBUS - PA = 64
unsigned16
1
8
0x0300
Profile Revision
Profile 3.0
unsigned16
1
9
0
Execution Time
f0r future use
unsigned8
1
10 54
NumberOfParameters
number of parameters
unsigned16
1
11 0x01b7
Address of VIEW 1
Index of view 1
unsigned16
1
12 1
Number of View Lists
Number of views
unsigned8
1
STD
111
1
0
ST_REV
Identification / device / statistic rev.-no. /
Function Block: counter which is incremented
at any change of configuration parameters
unsigned16
1
N
x
STD
112
2
Analyser
TAG_DESC
Unique tag in the system which can be used
by the user
visible_string
32
S
x
x
STD
113
3
0
STRATEGY
Strategy
unsigned16
1
S
x
x
STD
114
4
0
ALERT_KEY
User can write value for alert handling
unsigned8
1
S
x
x
STD
115
5
0x08
TARGET_MODE
Target mode of block = Auto
unsigned8
1
S
x
x
STD
116
6
MODE_BLK
Set block mode
ds37
1
D
x
1
0x08
Actual
Actual mode
2
0x88
Permitted
Permitted modes: Auto, O/S, MAN
3
0x08
Normal
Set mode in normal operation
STD
117
7
ALARM_SUM
Alarm status
ds42
1
D
x
1
0x0000
Current_Alarm
Current Alarm
2
0x0000
Unacknowledged
Not acknowledged
3
0x0000
Unreported
Not reported
4
0x0000
Disabled
Disabled
MAND
118
8
/
0.23
SOFTWARE_REVISION
Software Revision
visible_string
16
D
x
MAND
119
9
HARDWARE_REVISION
Hardware Revision
visible_string
16
D
x
MAND
120 10
42
DEVICE_MAN_ID
Manufacturer
unsigned16
1
C
x
MAND
121 11
DEVICE_ID
Device identification (unique)
visible_string
16
C
x
MAND
122 12
DEV_SER_NUM
Device serial number
visible_string
16
D
x
MAND
123 13
0x000000
00
DIAGNOSIS
Detailed device informations (bit coded)
octet_string
4
D
x
OPT
124 14
DIAGNOSIS_EXTENSION
Extended device information
octet_string
6
D
MAND
125 15
0xBBBF0
000
DIAGNOSIS_MASK
Bits supported by DIAGNOSIS
octet_string
4
C
x
OPT
126 16
DIAGNOSIS_MASK_EXTENSION Bits supported by DIAGNOSIS_EXTENSION
octet_string
6
C
OPT
127 17
CE,
NE21. Ex-
certificatio
n see
plate
DEVICE_CERTIFICATION
Device certification like EX, CE
visible_string
32
C
x
OPT
128 18
2457
WRITE_LOCKING
Password
unsigned16
1
N
x
x
OPT
129 19
0
FACTORY_RESET
Reset to Default-Values
unsigned16
1
S
x
x
OPT
130 20
descriptor DESCRIPTOR
visible_string
32
S
x
x
OPT
131 21
message DEVICE_MESSAGE
Message
visible_string
32
S
x
x
OPT
132 22
01.01.200
0
DEVICE_INSTAL_DATE
Date of device installation
octet_string
16
S
x
x
OPT
133 23
0
LOCAL_OP_ENA
Local operation enable
unsigned8
1
N
x
x
MAND
134 24
1
IDENT_NUMBER_SELECTOR
Profile analyser spec. (0) Profile spec. (3)
Manufacterer spec. (1) DP-Ident Number
unsigned8
1
S
x
x
OPT
135 25
HW_WRITE_PROTECTION
Hardware- Write Protection
unsigned8
1
D
x
136 26
bis
reserved by PNO
142 32